The AC Drive shall offer programmable DC 
injection braking that will brake the AC motor 
by injecting DC current and creating a 
stationary magnetic pole in the stator. The 
level of current will be adjustable between 50-
150% of rated current and available from 0.0-
30 seconds continuously. For continuous 
operation after 30 seconds, the current shall 
be automatically reduced to 50% of the 
nameplate current of the motor.
k. Sequencing logic will coordinate the engage 
and release thresholds and time delays for the 
sequencing of the AC Drive output, 
mechanical actuation and DC injection 
braking in order to accomplish smooth starting 
and stopping of a mechanical process.
2.10 OPERATOR CONTROLS
Note to Specifier: Select the operator control 
strategy that is appropriate for application 
requirements.
a. Industrial rated 22mm type control operators 
and pilot devices shall be door mounted and 
used independently of the keypad display to 
select operator control modes of [Hand-Off-
Auto, Communication-Auto-Off-Hand, Hand-
Off-Auto Start Stop, Hand-Off-Auto Local-
Remote]
. A door mounted manual speed 
potentiometer shall be used to control speed 
in the Hand mode of operation. 
Control modes shall function as follows:
1. Hand – The Hand mode shall allow 
manual operation of start, stop and speed 
control. The AC drive shall start when the 
control operator is in the Hand mode and 
run and at low speed setting of the drive or 
higher as required by the position of the 
manual speed potentiometer. This mode 
shall function as 2-wire control and 
automatically restart after a power outage 
or auto restart after fault. 
2. Off - The Off position of the control 
operator shall stop the AC drive and 
prevent it from restarting while in the Off 
position. This position shall also reset the 
AC Drive after a fault condition has 
occurred.
3. Auto - The Automatic mode shall receive 
an auto start contact rated 115VAC to 
control start and stop of the AC Drive. This 
contact shall also start and stop bypass (if 
used) when both the Automatic mode and 
Bypass modes of operations are selected. 
In Automatic mode the user shall remotely 
reset the AC Drive by opening and closing 
the Auto-start contact. Speed control shall 
be from a customer supplied [4-20mA, 0-
10Vdc] signal. 
4. Comm – The communication mode shall 
allow start, stop and speed control over 
network communication. (See 
Communication and Network 
Requirements.)
5. Start-Stop – Start / Stop pushbuttons shall 
provide 3-wire start stop control when the 
drive is in the hand position. The stop push 
button shall only be active in the Hand 
mode of operation.
6. Local Remote – Local / Remote selector 
switch shall provide speed reference 
control between a manual speed 
potentiometer and the remote speed 
reference when in the Auto mode of 
operation.
b. The AC Drive shall include door-mounted 
“Power On”, “AFC Run”, “AFC Fault”, “Auto/
Comm” mode and “Bypass” pilot lights. All 
pilot lights except ‘Power On” shall be Push-to-
Test configurations.
2.11 AC DRIVE SEQUENCING 
REQUIREMENTS
Note to Specifier: Specifying a run command relay 
provides an interface for customer supplied 
115Vac safeties and interlocks such as limit 
switches, flow or temperature switches. This 
control sequence ensures an AC Drive will stop in 
any control mode if safeties are opened. 
a. All Enclosed AC Drives shall have 115VAC 
interface and control sequencing. A Run 
Command Relay (RCR) shall function as a 
“request to run / run permissive” and close 
only when all customer wired safeties and 
control operator conditions calling for run are 
satisfied. The RCR relay shall prevent drive 
operation in any operating mode including 
network communication if the RCR relay 
conditions are not satisfied. A Drive Run Relay 
(DRR) shall provide run indication and 
interfacing to bypass (if used) and other 
system control sequencing as specified.