Schneider Electric 58 TRX User Manual

Page of 232
Class 8839 58M Enclosed AC Drives
Specifications
180
09/2003
©
 2000–2003 Schneider Electric All Rights Reserved
2.12 SYSTEM CONTROL AND INTERFACE 
REQUIREMENTS
Note to Specifier: Select the additional control 
functions that are appropriate for application 
requirements.
a. The following additional controls and interface 
requirements shall be provided:
1. Smoke Purge – The AC Drive shall provide 
a smoke purge interface relay. This relay, 
when closed will force the AC Drive to 
operate at the high speed setting (HSP) of 
the drive controller independent of any 
control setting or interlock. If full speed 
bypass is provided, the drive shall operate 
on bypass when the smoke purge relay is 
closed, independent of any system 
interlocks.
2. Fire / Freeze Stat Interlocks – The AC drive 
shall provide interlock wired to user 
terminals. Open interlocks shall prevent 
drive or bypass operation unless a smoke 
purge relay is provided and closed. 
3. Damper End Switch – The AC Drive shall 
provide a damper control circuit to 
coordinate the position of a damper to 
open before the motor is started either in 
AFC or Bypass. This circuit shall also 
provide maximum power of 40 VA sealed 
and 100 VA into the damper solenoid.
4. Seal Water Solenoid – The AC Drive shall 
provide 120 Vac / 50 VA to operate the seal 
water solenoid whenever the motor is 
energized.
5. Moisture Detection – The AC Drive shall 
provide a moisture detection circuit to 
indicate the presence of moisture in the 
windings of a submersible pump and 
prevent drive or bypass operation if 
moisture is detected.
6. Check Valve Sequencing – The AC Drive 
shall provide a circuit that shuts down the 
drive whenever a user supplied check 
valve limit switch does not open within a 
specified time. This circuit shall provide an 
illuminated reset push button to indicate 
improper sequence.
7. Motor Space Heater Sequencing – The AC 
Drive shall provide 120Vac/50VA to 
operate motor space heater when the 
motor is not running.
8. Motor Elapsed Time Meter – The AC Drive 
shall provide and elapsed time meter 
which operate whenever the motor runs.
9. Auxiliary Contacts – The AC Drive shall 
provide the following auxiliary contacts to 
indicate the following conditions:
2 N.O. contacts to indicate DRIVE RUN
1 N.C. contact to indicate DRIVE RUN
1 N.O. contact to indicate DRIVE FAULT
2 N.C. contacts to indicate DRIVE FAULT
1 N.O. contact to indicate BYPASS RUN
1 N.O. contact to indicate AUTO/COMM 
MODE
2.13 COMMUNICATION AND NETWORKING 
REQUIREMENTS 
Note to Specifier: Specifying a communication 
relay serves two important user safety concerns 
when using network communications:
1. Ensures that communication can not start an 
AC Drive when safety interlocks (limit, 
pressure, temperature or flow switches and/or 
Emergency Stop circuits) that are not part of 
the communication network are in an open 
state.
2. Ensures that network communications can not 
start, stop, or change the speed of an AC 
Drive, when a control mode other than 
communication is selected.
a. A Communication Mode Relay (CMR) shall 
close when operator controls are in the 
communication position. Contacts from the 
CMR relay shall pick up the run command 
relay if all safety conditions are met. Contacts 
from the CMR relay shall also provide pilot 
light indication when the AC Drive is in the 
communication mode. The CMR relay shall 
allow monitoring using network 
communication in any operator control mode. 
Network communication of start, stop, and 
speed control shall be limited to the 
communication mode when operator controls 
are in the communication position.   
b. The following Ethernet TCP/IP communication 
card and protocol shall be mounted and wired 
within the enclosed AC Drive.
c. The AC Drive shall accept an Ethernet 
communications card that includes embedded 
web-pages. 
1. The embedded web-pages shall provide 
the ability to configure, control, monitor 
and diagnose the AC drives via a standard 
web-browser such as Internet Explorer or