Connecting the auxiliary device to the GSM 
1.
Begin by installing the gate contact according to the manufacturers’ directions.
2.
Follow the instructions provided with the splice kit to connect the cable from the gate contact to 
the cable leading to the GSM.
3.
Attach the cable to the fence with UV resistant cable ties.  
Figure 8 Connecting the auxiliary device to the GSM
Figure 9 Auxiliary device wiring examples
Note
The contact closure input to the GSM MUST be voltage free.
Note
The GSM cable gland accepts cables with an OD of 2.9 to 6.4 mm 
(0.115 to 0.25 in.). 
The auxiliary input connector on the GSM accepts wire sizes between 16
and 26 AWG with a 1/4 in. strip (1.3 mm
2
 to 0.13 mm
2
 with a 6 mm strip).
Note
If the supervision resistor is installed inside the SK9 enclosure, the SK9 
should be mounted as close to the gate contact as possible.
battery +
13 cm (5 in.) leads
securely tighten the 16 mm 
proximity sensor (tamper)
auxiliary input
1 cm (0.4 in)
(5/8 in.) compression nut
connector
route the wires from the auxiliary device
(gate contact) along the inside edge of the
enclosure beside the battery or solar capacitor
keep the wires away from the proximity sensor
gate contact
normally closed
GSM AUX input
supervision
SK-9 enclosure
terminal block
resistor
gate contact
normally closed
GSM AUX input
supervision
SK-9 enclosure
terminal block
resistor