Universal Cellular Communicator
Input/output 
This page is used to program input or output modes, output activation events, polarity (N.C. or N.O.), reserved outputs and remote
activation SMS strings for reserved outputs.
Input/Output: double click on number to see the programming of the Input/output selected.
Label: enter an alphanumeric string of 16 characters max.
I/O Type: this column is used to program terminals T1, T2, T3, T4, T5 and T6 for the following mode:
– Input: select this mode to enable the corresponding terminal as the input line.
– Output: select this mode to enable the corresponding terminal as an open collector output.
Polarity: this box is used to program the output/input standby status:
– Normally Closed with the output/input in standby, the corresponding terminal is negative.
– Normally Open with the output/input in standby, the corresponding terminal is floating.
Select the corresponding Polarity to invert the parameter currently displayed.
Click on [+] Outputs to open the outputs column for the events to be programmed. The tick indicates that in the presence of
that event, the output will be turned on. Click on the boxes to insert / remove the check mark.
Programming the events linked to an output causes some of the boxes corresponding to that output to be disabled. Before you
can begin programming, you will need to remove the ticks from various boxes.
Panel Interconnection Fault: active the output if the panel is not present
Jamming Detect: active output when the device is under jamming attack.
Antenna Fault: active the output when the antenna is cut or shorted.
Tampers: when tamper is triggered.
PSTN Fault: active the output in case of PSTN fault.
GSM Fault: active the output in case of module power on fail, SIM issue, signal absent, no carrier.
No cellular Network: active the output in case of issue related to the data connection activation.       
IP receiver fail: active the output in all faulty cases related to the communication with IP receiver.
Power Fault: active the output in case of power fault.
Reserved output: when this option is selected, all other events selected to activate the corresponding output are ignored.
For remote activation the output will be activated through caller recognition 
or via an SMS command.
Control String: In this column, enter the string (maximum 16 alphanumeric characters) to be sent by SMS when you wish to
activate/deactivate the corresponding remote output. This feature will operate even if caller identification is not enabled.
Activation Confirmation: Use this column to select the type of confirmation you want when the output is activated. There
are 4 different options to choose from: None, Ring, SMS or Ring+SMS (the latter option is not available if the Control string
box has been left empty). The output activation confirmation is forwarded by means of a SMS when the output is activated by
SMS. (see the following table).
PROGRAMMING
EFFECTS
 Black List
White List
 Activation 
Confirmation
Call forwarded only if the communicator is switched to 
GSM Network
Confirmation 
Ring 
Disabled
Disabled
None
YES
NO
Disabled
Disabled
Ring
NO
YES
Disabled
Enabled
None
YES
NO
Disabled
Enabled
Ring
NO
YES
Enabled
Disabled
None
NO
NO
Enabled
Disabled
Ring
NO
YES
Enabled
Enabled
None
YES
NO
Enabled
Enabled
Ring
NO
YES