Digital Security Controls Ltd. 163G4005 User Manual

Page of 49
4005 Series
39
Main receiver APN:  enter the Access Point Name of the GPRS service provider being used. Enter the name of the IP
address service provider in this box.
Make sure to enter the correct APN for WAP/GPRS access - otherwise some functions may be limited (for more information,
please contact your customer support).
Main receiver User name: some providers may require a user name to validate communication. If needed, enter this information
here.
Main receiver Password: some providers may require a password to validate communication. If needed, enter this information
here.
Supervision 1 enabled: to enable supervision, select this option. The supervision option is ONLY available to the main
receiver. The supervision messages are not sent when the device is performing a voice call (on GSM). 
Supervision Time 1: set the Supervision time for the monitored receivers. It is possible to set a Supervision time between a
minimum of 60 seconds and a maximum of 65535 seconds, with steps of 1 second.
To comply with the EN50136-2:2013 standards the Supervision Time should be set less or equal to 3 minutes, and this function
should not be changed.
RECEIVER 2
In these fields enter the programming of the Receiver 2. The meaning of the Receiver 2 programming is the same of the Receiver
1
. If the Receiver 1 is set as Not Used, Receiver 1 will be disabled and Receiver 2 programming will be ignored; CID/SIA event
transmission to central station will be disabled).
If the Receiver 1 is set as: Primary, the Receiver 2 programming may be:
Not Used: the Receiver 2 is disabled; the communicator works in Single Receiver Mode with Receiver 1
Backup: the Receiver 2 works in the event Receiver 1 is down; the communicator works in Primary + Backup Mode.
Redundant: CID/SIA events will be sent to both Receiver 1 and Receiver 2; the communicator works in Redundant Mode.
Voice Message
This page is for managing the voice messages. On this page it is possible to record and play the voice messages. This page refers
to SMS/Voice Call for the association of voice messages to events. 
This communicator can storage up to 150 Messages, 8 sec. each. It manages the Upload/Download of the voice messages by PC
(hard disk, LAN, USB stick etc.) and manage the PC for recording and listening voice messages. Voice message will be upgradable.
Prerecorded audio files WAVE (.WAV) with several specifications may be used via the DLS 5 console. If wave files are loaded
on a USB stick, it is necessary to download them via the DLS 5 4.0 console.
The communicator will read the audio files that have the following format: eaudidx.bin, where eaud  is  the  fixed  prefix  that
identifies audio export file, idx is the file index in the range 001 to 999 and .bin is the file extension.
 PLAY Button - Press to listen to the voice message again.
 RECORD Button -Press to start recording a new voice message.
 STOP Button - Press to stop replaying or recording a voice message.
 PAUSE Button - Press to pause replaying or recording a voice message.
 ERASE Button - Press this button to erase the voice message on the Alarm Communicator.
 OPEN Button - Press this button to load prerecorded audio files, from PC (hard disk, LAN, etc.) or USB stick.
 SAVE Button - Press this button to save the voice Messages on a folder of PC.
When recording a message, a progress bar indicates (in real time) the time elapsed.