NOTE: When a valid IP address has been programmed, Ethernet Receiver 1 is enabled and will
communicate events over the Ethernet channel.
Ethernet Receiver 1 and Cellular Receiver 1 may be configured to communicate to the same
central station receiver. To configure the device to operate using this Common Receiver Mode
functionality, program Ethernet Receiver 1 and Cellular Receiver 1, IP address and port number
with identical values.
NOTE: When operating in Common Receiver Mode, Ethernet Receiver 1 account code will be
used for Ethernet and Cellular.
[104] Ethernet Receiver 1 Remote Port
Default (0BF5/3061)
This Section determines the remote port of Ethernet receiver 1. Valid range: 0000 - FFFF.
[105] Ethernet Receiver 1 Local Port
Default (0BF4/3060)
Use this Section to set the value of the local outgoing port. Set the value of this port when your
installation is located behind a firewall and must be assigned a particular port number as
determined by your central station 
system administrator. Valid range: 0000 - FFFF.
[106] Ethernet Receiver 1 Domain Name
Default (  )
Enter the Domain Name as 32 ASCII characters.
i
Programming this Section is not permitted on a UL/ULC listed system.
E
THERNET
 R
ECEIVER
 2 O
PTIONS
[111] Ethernet Receiver 2 Account Code
Default (0000000000)
The account code is used by the central station to distinguish between transmitters. The
account code is used when transmitting heartbeat signals to the central station receiver.
Signals received from the control panel will use the control panel account number. Valid range:
0000000001- FFFFFFFFFE. Programming all 0 or all F will cause a Module Configuration
Trouble (yellow LED=12 flashes).
NOTE: If both Ethernet Receiver 2 and Cellular Receiver 2 are the same receiver (IP and port
number are identical), Ethernet Receiver 2 account will be used for Ethernet and
Cellular.
[112] Ethernet Receiver 2 DNIS
Default (000000)
The DNIS is used in addition to the account code to identify the Communicator module at the
central station. Valid range: 000000 - 099999. Value is entered as leading 0 followed by the
5-digit DNIS. Format is BCD.
NOTE: Each Ethernet/Cellular receiver must be programmed with a unique DNIS.
[113] Ethernet Receiver 2 Address
Default (000.000.000.000)
Programming the Ethernet receiver 2 IP address with 000.000.000.000 will disable Ethernet.
Enter the Ethernet receiver 2 IP address. This address will be provided by your central station
system administrator. Format is 4 fields, each field is a 3-digit decimal. Valid range: 000-255.
NOTE: When a valid IP address has been programmed, Ethernet Receiver 2 is enabled and will
communicate events over the Ethernet channel.
Ethernet Receiver 2 and Cellular Receiver 2 may be configured to communicate to the same
central station receiver.
To configure the device to operate using this common receiver mode functionality, program the
Ethernet Receiver 2 and Cellular Receiver 2, IP address and port number with the same values.
When operating in common receiver mode the Ethernet Receiver 2 account code will be used
for communications over Ethernet and Cellular.
NOTE: Do not program Ethernet Receiver 1 and Ethernet Receiver 2 to communicate to same
receiver.