Digital Security Controls Ltd. 18LE2077 User Manual

Page of 51
29
NOTE: Each Ethernet/Cellular receiver must be programmed with a unique DNIS.
[203] Cellular Receiver 1 Address
Default (000.000.000.000)
Enter the Cellular Receiver 1 IP address. This information will be provided by your central station
system administrator. Each 3-digit segment of the address must be within a valid range of 000-
255.
NOTE: When a valid IP address has been entered, the Cellular is enabled and will communicate
events over the Cellular channel.
[204] Cellular Receiver 1 Port
Default (0BF5/3061)
This Section determines the port used by Cellular Receiver 1. Change the default value of this
port when your installation is located behind a firewall, and must be assigned a particular port
number as determined by your central station system administrator. Valid range: 0000 - FFFF.
NOTE: Programming this Section with 0000 will disable the receiver.
[205] Cellular Receiver 1 APN
Default (  )
The Access Point Name (APN) determines the Cellular network that the Communicator will
connect to. This information is available from your network carrier. Program this Section as 32
ASCII characters.
NOTE: When a SIM card with a custom APN is used, the unit will not have access to the Internet.
DLS and remote flash can still be done if Section [221] is programmed with a valid
Public APN.
[206] Cellular Receiver 1 Domain Name
Default (  )
i
Programming this Section is not permitted on a UL/ULC listed system.
Enter the Domain Name as 32 ASCII characters. This information will be provided by your
central station system administrator.
C
ELLULAR
 R
ECEIVER
 2 O
PTIONS
[211] Cellular Receiver 2 Account Code
Default (0000000000)
The account code is used by the central station to distinguish between different transmitters.
This account code is used when transmitting signals to the central station receiver. Signals
received on the panel will use the panel account number. Valid range: 0000000001  -
FFFFFFFFFE. 
NOTE: Programming this Section as all 0 or F will cause a Module Configuration Trouble (yellow 
LED = 12 flashes).
[212] Cellular Receiver 2 DNIS
Default (000000)
The DNIS is used in addition to the Account Code to identify the Communicator module at the
central station. Valid range: 000000 - 099999. Values are entered as a 0 followed by the 5
digit DNIS value. Format is BCD.
NOTE: Each Ethernet/Cellular receiver must be programmed with a unique DNIS.
[213] Cellular Receiver 2 Address
Default (000.000.000.000)
Enter the Cellular Receiver 2 IP address. This IP address will be provided by your central station.
Format is 4 fields, each field is 3-digit decimal. Valid range: 000 - 255.
NOTE: When a valid address has been entered, Cellular Receiver 2 is enabled and will
communicate events over the Cellular path.