Digital Security Controls Ltd. 18LE2077 User Manual

Page of 51
28
[114] Ethernet Receiver 2 Remote Port
Default (0BF5/3061)
This Section is used to program the port number used by Ethernet Receiver 2. Set the value of
this port when your installation is located behind a firewall, and must be assigned a particular
port number as determined by your central station system administrator. Valid range: 0000 -
FFFF.
NOTE: Do not program Ethernet Receiver 1 and Ethernet Receiver 2 Port with the same value.
[115] Ethernet Receiver 2 Local Port
Default (0BF9/3065)
Use this Section to program the value of the local outgoing port. You can set the value of this
port when your installation is located behind a firewall and must be assigned a particular port
number as determined by your network administrator. Valid range: 0000 - FFFF. 
NOTE: Do not program Ethernet Receiver 1 and Ethernet Receiver 2 Port with the same value.
[116] Ethernet Receiver 2 Domain Name
Default (  )
i
Programming this Section is not  permitted on a UL/ULC listed system.
Enter the Domain Name as 32 Character ASCII.
E
THERNET
 O
PTIONS
[124] Ethernet Test Transmission Time
Default (9999)
Enter a 4 digit number (0000-2359) using the 24-hour clock format (HHMM) to set the test
transmission time of day. 
Valid range: 00 - 23 hours (HH) and 00 - 59 minutes (MM). Programming a value of 9999 will
disable the test transmission time.
NOTE: The internal date and time will automatically be programmed when the unit
communicates with the primary receiver.
[125] Ethernet Test Transmission Cycle
Default (000000)
This value represents the interval between test transmissions, in minutes. Valid range: 000000
- 999999 minutes. Once the unit has sent the initial periodic test transmission, all future test
transmissions will be offset by the programmed number of minutes. See Sections [026] -
[029].
NOTE: Minimum value is 000005 minutes. Programming an interval that is less than 5 minutes
will disable test transmission.
C
ELLULAR
 R
ECEIVER
 1 O
PTIONS
[201] Cellular Receiver 1 Account Code
Default (0000000000)
The account code is used by the central station to distinguish between transmitters. This
account code is used when transmitting heartbeat signals to the central station receiver.
Signals received from the control panel will use the control panel account number. Valid range:
0000000001 - FFFFFFFFFE. Programming all 0 or all F will cause a Module Configuration
Trouble (yellow LED = 12 flashes).
[202] Cellular Receiver 1 DNIS
Default (000000)
The DNIS is used in addition to the account code to identify the Communicator module at the
central station. Valid range: 000000 - 099999. Values are entered as leading 0 followed by
the five digit DNIS. Format is BCD.
Table 13: Ethernet Test Transmission Interval
Test Transmission Interval
Daily
Weekly
Monthly
Programmed Minutes
001440
010080
043200