XT30/XT50 Installation Guide
18
COMPLIANCE
Central Station Burglar Alarm Units 
ANSI/UL 1610
23.1  Central Station
Digital Dialer Central Station (DACT) service for commercial application can be provided by adding a listed
local audible signal appliance and placing the XT30 or XT50 panel into the Model 349A Attack Resistant
Enclosure.
23.2  Remote Disarm
REMOTE DISARM must be programmed as NO.
23.3  Central Station
MESSAGE TO TRANSMIT programming for zones must not be set to LOCAL (L).
Household Fire Warning System  
ANSI/UL 985 NFPA 72 Specifications
24.1  Bell Output Definition
The bell output of the Model XT30/XT50 must be programmed to operate steady on burglary alarms and
temporal on fire alarms. See the XT30/XT50 Programming Guide.
24.2  Household System
An alarm sounding device must be installed indoors so that it is clearly heard in all sleeping areas.
24.3  Household Fire Warning
Recognized limited energy cable must be used for connection of all initiating, indicating, and supplementary
devices.
24.4  Wireless Supervision Time
The Zone Information Supervision Time must be 3 minutes for fire devices. See the XT30/XT50 Programming
Guide.
24.5  Wireless Fire Verification
When used, the Model 1161 and 1162 wireless smoke detectors must not be programmed as Fire Verification
(FV) zone type. See the XT30/XT50 Programming Guide.
24.6  Battery Standby
For UL listed applications, the panel must have 24 Hour battery standby operation. The Model 364 battery
should not be used for fire installations.
24.7  Alarm Verification
Alarm Verification must only be enabled on smoke detectors that do not employ an integral alarm
verification feature.
24.8  Model 860
When using the Model 860 Relay Output, a fire and non-fire device must not share a relay.
24.9  Test Frequency
The Test Frequency option must be programmed to send a report at least once every 30 days.
California State Fire Marshal Specifications
25.1  Bell Output Definition
The bell output of the Model XT30/XT50 must be programmed to operate steady on burglary alarms and
temporal on fire alarms.