Digital Monitoring Products Inc PC0128 User Manual
XT30/XT50 Installation Guide
Digital Monitoring Products
19
COMPLIANCE
False Alarm Reduction Programmable Options
ANSI/SIA CP-01-2010
26.1 Shipping Defaults and Recommended Programming
SIA CP-01 FEATURE
PARAGRAPH # AND
DESCRIPTION
DMP PROGRAMMING
GUIDE LT-0981
SECTION #
REQUIREMENT
RANGE
SHIPPING
DEFAULT
RECOMMENDED
PROGRAMMING*
4.2.2.1 Exit Time
8.6 Exit Delay
Required
(Programmable) 45 sec. - 250 sec.
60
Seconds
60 Seconds
4.2.2.2 Progress
Annunciation
13.14 Prewarn Address Allowed
Individual keypads
may be disabled per
zone
All
keypads
enabled
All keypads enabled
4.2.2.3 Exit Time Restart 8.6 Exit Delay
Required Option For re-entry during
exit time
Enabled
Enabled
4.2.2.5 Auto Stay Arm on
Unvacated Premises
8.17 Occupied Premise
- See Install Guide
Required Option
(except for
remote arming)
Occupied Premise NO/
YES option
Enabled
Enabled Yes
for Residential
Applications
4.2.4.4 Exit Time and
Progress Annunciation/
Disable - for Remote Arm
Not Available on
Remote Arming
Allowed Option
Progress Annunciation
Always disabled for
Remote Arming
Not
Available
Remote Arming not
allowed for CP-01
installations.
4.2.3.1 Entry Delay(s)
8.5 Entry Delay
Required
(Programmable) 30 sec. – 240 Sec. **
30
Seconds
At least 30 Seconds
**
4.2.5.1 Abort Window –
for Non-Fire Zones
3.3 Transmit Delay
Required Option Disable by zone or
zone type
Enabled
NT DY EX
Zone
Enabled
4.2.5.1 Abort Window
Time – for Non-Fire
Zones
3.3 Transmit Delay
Required
(Programmable)
20 sec., 30 sec., or
40 sec.
**
30
Seconds
At least 20 Seconds
**
4.2.5.1.2 Abort
Annunciation
3.3 Transmit Delay
Required Option Annunciate that no
alarm was transmitted Yes
Yes
4.2.5.4.1 Cancel
Annunciation
Always Enabled - Not
Programmable
Required Option
Annunciate that
a Cancel was
transmitted (S49)
Always
Enabled
Yes
4.2.6.1 & 4.2.6.2 Duress
Feature
User Code + 1 =
Ambush Code Not
Available
Allowed Option
No 1 + derivative of
another user code/no
duplicates with other
user codes
Code +1
Always
Disabled
Not Programmable
4.3.1 Cross Zoning
13.16 Cross Zone
Required Option Yes/No Zone
Programming
No
Enabled using two or
more programmed
zones
4.3.1 Programmable
Cross Zoning Time
8.7 Cross Zone Time
Allowed
4 sec. - 250 sec.
0 Seconds Per walk path in
protected premises
4.3.2 Swinger Shutdown
Not Available — Always
On
Required
1-6 trips
2 trips
2 trips
4.3.2 Swinger Shutdown
Disable
13.13 Swinger Bypass
Allowed
For non-police
response zones
Yes
Enabled (all zones)
4.3.3 Fire Alarm
Verification
13.5 Zone Type
Required Option FV Type Zone
No
Yes as required (unless
sensors can self verify)
4.5 Call Waiting Cancel
3.17 First Telephone
Number
Required Option Include *70P in
Telephone Number
Disabled
Enabled if user has
call waiting
4.6.3 System Test
17.5 Walk Test
Allowed
Test all protection
devices
N/A
N/A
4.6.5 Communications
17.5 Walk Test
Not Allowed
N/A
N/A
N/A
* Programming at installation may be subordinate to other listed requirements for the intended application.
** For listed Installations, combined Entry Delay and Transmit Delay should not exceed 1 minute.