Digital Monitoring Products Inc PC0132 User Manual

Page of 22
 
9800 Series Keypad Installation Guide 
7
Standby Battery
The keypad rechargeable battery provides 24 hours of backup battery power when 
primary DC power is not available. It is shipped already installed inside the keypad. 
The battery is intended for backup power only and not to operate the keypad on 
a daily basis. If the battery is low, or not plugged into the internal J3 battery 
connector, a low battery condition is indicated by the panel when the battery falls 
below 3.62 volts. To restore the keypad from a low battery state, the voltage must 
be above 3.62.
Use the following steps to replace the battery. DMP recommends replacing the 
battery every 3 years under normal use.
Note: If removing the keypad from service, disconnect the power supply connector 
from the back of the keypad to avoid discharging the battery.
Battery Replacement
1. Disconnect the battery lead connector from the keypad J3 battery header.
2. Squeeze the battery straps to remove the standby battery.
3. Observe polarity and connect the battery lead connector to the keypad J3 
battery header. See Figure 11.
4. Place the new battery (DMP Model 9800BAT) on the keypad PCB and replace 
the battery straps.
5. Properly dispose of the used battery. 
Caution: Risk of fire, explosion, and burns. Do not disassemble, heat above 
212°F (100°C), or incinerate.
Figure 11: Battery Connection
Battery Strap
Battery
J3 Battery
Connection