COMMUNICATION
Communication
22.1 Communication
The 
Communication section allows you to configure the communication settings 
for the XTLplus panel. After choosing the Communication Type, continue through 
the list of options.
22.2 
Account Number
Enter the account num ber sent to the receiver.
The range of account numbers are 1 to 65535. For account numbers of four digits 
or less, you do not have to enter leading zeros. The panel automatically right 
justifies the account number.
22.3 
Transmission Delay
Enter the number of seconds (15 to 45 seconds) the panel waits before sending 
burglary alarm reports to the receiver. The wireless siren and relay outputs are not 
delayed during this period. Enter 0 (zero) to disable this function. The default is 30.
22.4 
Communication Type
This specifies the communication method the panel uses to contact the receiver. 
Press any select key to display the following communication options:
WIFI - Network communication to DMP Model SCS-1R or SCS-VR Receivers.
CEL - This option allows communication over the cellular network using the 265C 
Cellular Communicator to DMP Model SCS-1R or SCS-VR Receivers.
NONE
 - For local systems. Selecting this ends communication programming.
Note: If automatic cellular activation is unsuccessful, cellular communication 
must be activated using the Activate Cell option provided in Diagnostics Function 
located in the Appendix.
22.5 
Backup Cellular
 
Backup Cellular option is available if COMM TYPE is set for WIFI. The Backup 
Cellular tries to send the message after the main communication fails for 60 
seconds on WIFI. If the backup dialer fails then the message is discarded.
22.6 
Test Time
Press COMMAND to enter the Test Time. Enter the time of day the panel sends the 
test report to the SCS-1R Receiver. Use entries between 12:00 to 11:59 and then 
choose AM or PM.
22.7 
Test Days
 
Enter how often the panel test report is sent to the receiver. Enter from 1 to 60 
days. Enter zero to disable the test report. Default is 1 (one) day. This option only 
displays if a test time is entered.
22.8 
Check In Minutes
Check-in reports are a method of supervising the panel for communication with the 
receiver. Enter the number of minutes between check-in reports. Select from 0 or 
3-240 minutes. Enter 0 (zero) to disable the check-in option. Default is 200.
Note: If Cell Check-in option is used, additional cell charges may apply.
22.9 
Fail Time
Fail Time allows the SCS-1R or SCS-VR receiver to miss a defined number of  
check-ins before logging that the panel is missing. For example, if CHECKIN is 20 
and FAIL TIME is 30, the SCS-1R receiver only indicates a Panel Not Responding 
after 30 minutes. The FAIL TIME must be equal to or greater than the CHECKIN 
minutes: If the CHECKIN is 20 minutes, the FAIL TIME must be 20 or more. The 
maximum FAIL TIME is 240 minutes. Select from 0 or 3-240 minutes. The default 
FAIL TIME is 240 minutes.
Closing Wait operation: Closing Wait operation is activated if Fail Time is set 
to 3 minutes and O/C Reports in System Reports is YES and O/C User reports in 
Communication Programming is set to YES.
Closing Wait provides a delay time before a monitored system arms until the 
panel receives an acknowledgment of the closing report from the central station 
receiver. During the delay, the keypad displays ONE MOMENT .  .  .
Once the closing is acknowledged from the SCS-1R receiver, the keypad buzzes 
for one second and then displays an armed status message. If the primary 
communication fails, the message LOCAL ALARM ONLY appears.
COMMUNICATION
ACCOUNT NO:
XMIT DELAY:  
30
COMM TYPE:
CELL
WIFI CEL NONE
BACKUP CELL
  
NO YES
TEST TIME   
00:00 AM
TEST DAYS:  
1
 
CHECKIN:
200
FAIL TIME:  
240