Digital Monitoring Products Inc PC0181 User Manual

Page of 58
Digital Monitoring Products
 
XTLplus Installation and Programming Guide
16
COMMUNICATION
22.10 
Send Communication Trouble
Enable communication fail notification by selecting YES at COMM TRBL. Select NO 
to disable. Default is YES.
When COMM TRBL is YES and the panel detects a failure of communication, the 
panel sends an S72 (Comm Trouble) message through a backup communication 
method with notification of the failure. If both primary and secondary methods 
of communication fail, then two S72 messages will be sent via the third 
communication method, if programmed. The keypad sounds a continuous tone, 
which may be silenced by pressing any key, and displays “COMM  -TRBL”.
When communication is restored, the panel sends an S73 (Comm Restored) 
message through the primary communication. The “COMM -TRBL” message is 
removed from the keypad display and the keypad sounder is turned off, if no other 
trouble messages are pending.
Note: If the primary or secondary communication type is CELL, S72 and S73 
messages include the cell signal strength as a -dBm value.
22.11 
First Cell APN
Enter the first APN (Access Point Name). This allows an access point for cellular 
communication and is used to connect to a DNS network. The APN may contain two 
lines of 16 characters to equal 32 characters. Default is set to SECURECOM400.
22.12 
Second Cell APN
Enter the second APN (Access Point Name). This works as a backup in case the first 
APN fails. The APN may contain two lines of 16 characters to equal 32 character 
Default is set to SECURECOM400.
22.13 
Receiver 1 Programming
Allows you to set the options for the first receiver the panel attempts to contact 
when sending reports. The XTLplus supports communication to two receivers.
22.14 
Alarm Reports
YES enables Abort, Alarm, Alarm Restoral, Alarm Bell Silenced, Ambush, Exit Error, 
and System Recently Armed reports to be sent to this receiver. Default is YES.
22.15 
Supervisory/Trouble Reports
YES enables Supervisory, Trouble, Trouble Restoral, Force Armed, Late to Close, 
and Fault reports to be sent to this receiver. Default is YES.
22.16 
Opening/Closing and User Reports
YES enables Opening/Closing, Code Changes, and Bypass reports by user to be sent 
to this receiver. Default is NO.
22.17 
Test Report
Enter 
YES to enable the Recall Test report to be sent to this receiver.
22.18 
First IP Address
Enter the first (primary) IP address where the panel sends network or cellular 
information. Enter all 12 digits and leave out the periods. For example, enter IP 
address 192.168.0.250 as 192168000250. The periods display automatically.
The message is sent using first Cell APN and the first IP Address. If no 
acknowledgment is received, first Cell APN and the second IP address are used, 
followed, if needed, by second Cell APN and first and second IP addresses, 
respectively.
22.19 
First IP Port
Enter the first IP port number to be used in conjunction with the first IP Address. 
The IP port identifies the port used to communicate messages to and from the 
panel. The default IP Port setting is 2001.
22.20 
Second IP Address
Enter the second (secondary) IP address where the panel sends network or cellular 
information. Enter all 12 digits and leave out the periods. For example, enter IP 
address 192.168.0.250 as 192168000250. The periods display automatically.
22.21 
Second IP Port
 
Enter the second IP port number to be used in conjunction with the second IP 
address. The IP port identifies the port used to communicate messages to and from 
the panel. The default IP Port setting is 2001.
COMM TRBL NO  YES
SECURECOM400
-
FIRST CELL APN
SECURECOM400
-
SECOND CELL APN
RECEIVER 1 PROG
ALARM
NO  YES
SPV/TRBL  NO  YES
O/C USER  NO YES
TEST RPT  NO  YES
FIRST IP ADDR 
000.000.000.000 
FIRST IP PORT
    
2001
SECOND IP ADDR
000.000.000.000 
SECOND IP PORT
    
2001