Digital Monitoring Products Inc PC0181 User Manual

Page of 58
XTLplus Installation and Programming Guide 
Digital Monitoring Products
17
COMMUNICATION
22.22 
Receiver 2 Programming
Allows you to set the options for the second receiver the panel attempts to contact 
when sending reports. The XTLplus supports communication to two receivers. If 
you select 
YES for any of the Receiver 2 options, you must have at least one IP 
address programmed in Receiver 2 programming. Receiver 2 defaults are set to 
NO.
22.23 
Alarm Reports
YES enables Abort, Alarm, Alarm Restoral, Alarm Bell Silenced, Ambush, Exit Error, 
and System Recently Armed reports to be sent to this receiver. Default is
 NO.
22.24 
Supervisory/Trouble Reports
YES enables Supervisory, Trouble, Trouble Restoral, Force Armed, Late to Close, 
and Fault reports to be sent to this receiver. Default is
 NO.
22.25 
Opening/Closing and User Reports
YES enables Opening/Closing, Code Changes, and Bypass reports by user to be sent 
to this receiver. Default is 
NO.
22.26 
Test Report
YES
 enables the Recall Test report to be sent to this receiver. Default is NO.
22.27 
First IP Address
Enter the first (primary) IP address where the panel sends network or cellular 
information. Enter all 12 digits and leave out the periods. For example, enter IP 
address 192.168.0.250 as 192168000250. The periods display automatically.
The message is sent using first Cell APN and the first IP Address. If no 
acknowledgment is received, first Cell APN and the second IP address are used, 
followed, if needed, by second Cell APN and first and second IP addresses, 
respectively.
22.28 
First IP Port
 
Enter the first IP port number to be used in conjunction with the First IP Address. 
The IP port identifies the port used to communicate messages to and from the 
panel. The default IP Port setting is 2001.
22.29 
Second IP Address
Enter the second (secondary) IP address where the panel sends network or cellular 
information. Enter all 12 digits and leave out the periods. For example, enter IP 
address 192.168.0.250 as 192168000250. The periods display automatically.
22.30 
Second IP Port
Enter the second IP port number to be used in conjunction with the second IP 
Address. The IP port identifies the port used to communicate messages to and from 
the panel. The default IP Port setting is 2001.
Network Options
Network Options are provided to define the network configuration for the panel. This information will be 
used during communication of messages via network.
Note: Wi-Fi must be selected as Communication Type in the Communication section for Wi-Fi Setup  
to display.
Note: IP addresses and port numbers may need to be assigned by the network administrator. When 
entering an IP, Gateway, or Subnet Mask address be sure to enter all 12 digits and leave out the periods. 
For example, IP address 192.168.000.250 is entered as 192168000250.
23.1 
Network Options
This option is for configuring the desired network settings. Press any select key to 
select.
23.2 
Wi-Fi Setup
This option is for connecting to the desired Wi-Fi network and will display only 
when Comm Type is set to Wi-Fi. Press any select key to select.
WPS  LIST  MANUAL displays. Press the first select key to choose WPS to 
automatically connect to a WPS enabled router. Press the second select key to 
choose LIST and see the name and signal strength of any Wi-Fi routers in range. 
Press the third or fourth select key to choose MANUAL and enter the name of the 
Wi-Fi router you wish to connect to. Pressing COMMAND displays TEST. To select 
TEST press the first select key to verify connection of your system to the Wi-Fi 
network.
RECEIVER 2 PROG
ALARM
NO YES
SPV/TRBL  NO YES
O/C USER  NO YES
TEST RPT  NO YES
FIRST IP ADDR 
000.000.000.000 
FIRST IP PORT
    
2001
SECOND IP PORT
    
2001
NETWORK OPTIONS
NETWORK OPTIONS
WPS LIST MANUAL
TEST