Digital Monitoring Products Inc PC0181 User Manual
XTLplus Installation and Programming Guide
Digital Monitoring Products
17
COMMUNICATION
22.22
Receiver 2 Programming
Allows you to set the options for the second receiver the panel attempts to contact
when sending reports. The XTLplus supports communication to two receivers. If
you select
YES for any of the Receiver 2 options, you must have at least one IP
address programmed in Receiver 2 programming. Receiver 2 defaults are set to
NO.
22.23
Alarm Reports
YES enables Abort, Alarm, Alarm Restoral, Alarm Bell Silenced, Ambush, Exit Error,
and System Recently Armed reports to be sent to this receiver. Default is
NO.
22.24
Supervisory/Trouble Reports
YES enables Supervisory, Trouble, Trouble Restoral, Force Armed, Late to Close,
and Fault reports to be sent to this receiver. Default is
NO.
22.25
Opening/Closing and User Reports
YES enables Opening/Closing, Code Changes, and Bypass reports by user to be sent
to this receiver. Default is
NO.
22.26
Test Report
YES
enables the Recall Test report to be sent to this receiver. Default is NO.
22.27
First IP Address
Enter the first (primary) IP address where the panel sends network or cellular
information. Enter all 12 digits and leave out the periods. For example, enter IP
address 192.168.0.250 as 192168000250. The periods display automatically.
The message is sent using first Cell APN and the first IP Address. If no
acknowledgment is received, first Cell APN and the second IP address are used,
followed, if needed, by second Cell APN and first and second IP addresses,
respectively.
22.28
First IP Port
Enter the first IP port number to be used in conjunction with the First IP Address.
The IP port identifies the port used to communicate messages to and from the
panel. The default IP Port setting is 2001.
22.29
Second IP Address
Enter the second (secondary) IP address where the panel sends network or cellular
information. Enter all 12 digits and leave out the periods. For example, enter IP
address 192.168.0.250 as 192168000250. The periods display automatically.
22.30
Second IP Port
Enter the second IP port number to be used in conjunction with the second IP
Address. The IP port identifies the port used to communicate messages to and from
the panel. The default IP Port setting is 2001.
Network Options
Network Options are provided to define the network configuration for the panel. This information will be
used during communication of messages via network.
Note: Wi-Fi must be selected as Communication Type in the Communication section for Wi-Fi Setup
to display.
Note: IP addresses and port numbers may need to be assigned by the network administrator. When
Note: IP addresses and port numbers may need to be assigned by the network administrator. When
entering an IP, Gateway, or Subnet Mask address be sure to enter all 12 digits and leave out the periods.
For example, IP address 192.168.000.250 is entered as 192168000250.
23.1
Network Options
This option is for configuring the desired network settings. Press any select key to
select.
23.2
Wi-Fi Setup
This option is for connecting to the desired Wi-Fi network and will display only
when Comm Type is set to Wi-Fi. Press any select key to select.
WPS LIST MANUAL displays. Press the first select key to choose WPS to
automatically connect to a WPS enabled router. Press the second select key to
choose LIST and see the name and signal strength of any Wi-Fi routers in range.
Press the third or fourth select key to choose MANUAL and enter the name of the
Wi-Fi router you wish to connect to. Pressing COMMAND displays TEST. To select
TEST press the first select key to verify connection of your system to the Wi-Fi
network.
RECEIVER 2 PROG
ALARM
NO YES
SPV/TRBL NO YES
O/C USER NO YES
TEST RPT NO YES
FIRST IP ADDR
000.000.000.000
000.000.000.000
FIRST IP PORT
2001
SECOND IP PORT
2001
NETWORK OPTIONS
NETWORK OPTIONS
WPS LIST MANUAL
TEST