7.  Use wall anchors and screws to secure into place. 
Attach the sensor to the mounting plate. 
8.  When testing is completed the PIR can be securely 
attached to its mounting plate by screwing the smallest 
enclosed screw into the hole at the top of the mounting 
plate. 
Setting the Sensitivity 
The PIR has two sensitivity settings (standard and high 
sensitivity). The sensor is set to standard sensitivity at the 
factory. This sensitivity is preferred for most applications and 
provides the best immunity to false alarms. 
Note: If the shorting jumper is not used or is placed 
incorrectly, the sensor defaults to standard sensitivity. 
Figure 5: Sensitivity Pin Locations 
 
CAUTION: High sensitivity should only be used in 
environments where the room temperature is very 
stable. 
1.  Remove the mounting plate by depressing the button on 
the top of the sensor body. With the opposite hand pull 
the mounting plate away from the body of the sensor. 
2.  Remove the PIR cover by depressing the three tabs  
3.  Locate the sensitivity pins under the battery on the right 
side of the PIR when looking at the front of the PIR. 
4.  To change to high sensitivity move the shorting jumper 
to the pair of pins that are closer to the top of the PIR 
See Figure 5. 
5.  Walk test the PIR to verify the sensitivity. 
The difference between the two settings are indicated in 
Figures 6 and 7.below. 
Figure 6: Standard Sensitivity Setting 
 
Figure 7: High Sensitivity Setting