Installation Guidelines
Installation Guidelines
Observe the following guidelines when installing the
receiver module:
receiver module:
❑
Concord
™
systems can accommodate a maximum of
76 wireless sensors/zones.
❑
In Concord systems, up to 16 SuperBus 2000 devices
can be connected to the panel (SuperBus 2000 Touch-
pads, Receivers, HIMs, HOMs, ESMs, etc.).
can be connected to the panel (SuperBus 2000 Touch-
pads, Receivers, HIMs, HOMs, ESMs, etc.).
❑
Each bus device must have a different unit number.
❑
Leave 10-inches above the module for the antennas.
❑
If mounting the module inside the panel cabinet, use a
support standoff included with the Concord panel.
support standoff included with the Concord panel.
If mounting the module away from the panel, use the
wire length guidelines in Table 2.
wire length guidelines in Table 2.
❑
Avoid areas that are likely to expose the module to
moisture.
moisture.
❑
Avoid areas with excessive metal or electrical wiring,
including furnace and utility rooms.
including furnace and utility rooms.
If unavoidable, mount on or near metal with the anten-
nas extending above the metallic surfaces, as shown in
Figure 2.
nas extending above the metallic surfaces, as shown in
Figure 2.
Figure 2. Mounting on or Near Metal
Tools and Supplies
❑
Screwdrivers
❑
Drill with bits
❑
Mounting screws and anchors (included)
❑
2 antennas (included)
❑
4-conductor, 22-gauge or larger, stranded wire
❑
Support standoff (included with Concord cabinet)
❑
¼-inch press-fit reed switch and magnet (not included)
❑
Small hammer
Installation
The module can be mounted inside the panel cabinet or on
any interior wall (protected from the elements).
any interior wall (protected from the elements).
CAUTION
To prevent damaging the panel or module, remove the
panel AC power transformer and disconnect the
backup battery before installation.
panel AC power transformer and disconnect the
backup battery before installation.
CAUTION
You must be free of static electricity before handling
circuit boards. Wear a grounding strap or touch a bare
metal surface to discharge static electricity.
circuit boards. Wear a grounding strap or touch a bare
metal surface to discharge static electricity.
Figure 3. Removing the Cover
To mount the module on a wall:
1.
Remove the panel AC power transformer and discon-
nect the backup battery.
nect the backup battery.
2.
Remove the module cover and set it aside (Figure 3).
3.
Hold the base against the mounting surface and mark
the three mounting holes (Figure 1). Remember to
leave at least 10 inches
the three mounting holes (Figure 1). Remember to
leave at least 10 inches
above the base for the
antennas.
4.
Drill holes and insert the appropriate anchors.
5.
Secure the back-plate to the wall with included pan-
head screws.
head screws.
To mount the module in a Concord panel cabinet:
1.
Remove the panel AC power transformer and discon-
nect the backup battery.
nect the backup battery.
2.
Remove and discard the module cover (Figure 3).
Table 2. Maximum Module Wire Lengths
Wire Gauge
(Unshielded
or Shielded)
Max. Wire Length Between
Module and Concord Panel
18
2,800 feet
22
1,100 feet
METAL
METAL
8836G02A.DS4
PRESS DOWN
HERE AND PULL
AWAY FROM BASE
HERE AND PULL
AWAY FROM BASE