X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
External  Under Temperature  – This alarm will be active when the external 
temperature falls below the activation temperature.  It will not deactivate until the 
temperature rises above the cancellation temperature.
Controller  Over Temperature  – This alarm will be active when the internal 
temperature exceeds the activation temperature.  It will not deactivate until the 
temperature falls below the cancellation temperature.
Controller Under Temperature – This alarm will be active when the internal 
temperature falls below the activation temperature.  It will not deactivate until the 
temperature rises above the cancellation temperature.
13.5.3 - Voltage Alarms
Figure 25 - Alarm Matrix WEB Applet - voltage alarm settings (typical)
Over Voltage – This alarm will activate if the system voltage exceeds this threshold.  
When the voltage falls below the cancellation threshold the alarm will be canceled.
Low Voltage – This alarm will activate if the system voltage falls below this 
threshold.  When the voltage rises above the cancellation threshold the alarm will 
be canceled.
Low Low Voltage – This alarm will activate if the system voltage falls below this 
threshold.  When the voltage rises above the cancellation threshold the alarm will 
be canceled.
13.5.4 - Current Alarms
Figure 26 - Alarm Matrix WEB Applet - voltage alarm settings (typical)
Rectifier Over Current – This alarm will activate if the rectifier current rises 
above this threshold.  The alarm will be canceled when the current falls below the 
cancellation threshold.