Unique Broadband Systems Ltd. DRU2KW User Manual
Page 33
X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
Battery Capacity (Amp-Hours). This is the capacity of one battery string.
Total Installed Capacity. This is simply the number of strings multiplied by the
Total Installed Capacity. This is simply the number of strings multiplied by the
battery capacity. This figure is only for reference, it is not currently used for any
active functions.
Charge Limit (Amps). This is used to limit the battery charging current. Battery
Charge Limit (Amps). This is used to limit the battery charging current. Battery
charge limiting is done by reducing the rectifier voltage to maintain the battery
charging current at the set level.
Enable Charge Limiting Check box. Check this box if you wish to enable the
Enable Charge Limiting Check box. Check this box if you wish to enable the
battery charge limit feature.
13.3.4 - Equalization
Figure 16 - Installation WEB Applet - float & tc tab (typical)
The Equalization tab deals with battery equalization. Some types of batteries must
not be equalized or boosted. Please consult the datasheet of the batteries being used
before using these features. Incorrectly applied equalization can damage the batteries.
The settings are as follows:
Enable Equalization checkbox. This enables the equalization functions. If not
checked, no equalization or boost functions may be done.
Enable Equalize at end of charging checkbox. To provide a boost to charging
Enable Equalize at end of charging checkbox. To provide a boost to charging
the batteries more quickly, the voltage applied to the batteries may be boosted for a
short time to the higher voltage. Check this box to enable this feature.