 Xeon Phi™ Coprocessor Datasheet
Document ID Number: 328209 003EN
34
For the region A-B, the cooling solution must maintain the case temperature below 
95
°
C which will in turn maintain the coprocessor silicon junction temperature below 
104
°
C. Assuming an air-cooled heat sink, at a maximum coprocessor power dissipation 
of 198W (
) and an inlet air temperature of 45
°
C, the following equation 
between coprocessor junction-to-case and case-to-air heat sink rating can be used to 
determine the minimum necessary performance of a cooling system:
T
junction
=
jc
 * CPU
power
 + 
ca_req
 * CPU
power
 + T
ambient
The heat sink must have a 
ca_req 
value adequate to keep the coprocessor junction 
temperature at or below 104
°
C. The value for 
jc 
is a characteristic of the Intel
®
 Xeon 
Phi™ coprocessor and may be treated as 0.047, a constant.
As the coprocessor power level goes down (region B-C), it is desirable to keep the 
junction temperature at or below a target temperature, here shown at 82
°
C. Since each 
coprocessor is programmed at the factory with the actual control temperature (T
control
), 
a sophisticated cooling system may continuously read the junction temperature from 
the card SMC and compare it to the programmed T
control 
to adjust airflow. The change 
in airflow over an air cooled heat sink affects the 
ca 
value. It is common to reduce fan 
speed when maximum airflow is not needed to save power, reduce noise, or both.
In the B-C region, even though T
junction
 is at a constant value, T
case
 actually goes up a 
little bit at lower power consumption levels. This is because a variable fan speed results 
in a variable 
ca
, but a fixed 
jc
.
Finally, in the C-D region where the coprocessor consumes very little power, an air 
cooled heat sink using a variable fan speed to maintain a target junction temperature 
may slow the airflow down too much. If the airflow is too low, the junction temperature 
may be maintained properly, but the exhaust air temperature approaches the junction 
temperature. Data center design considerations, including safety, may dictate that a 
maximum allowable exhaust air temperature, such as 70
°
C, which in turn will set a 
maximum limit on 
ca
.
Figure 3-17 SE10X/7120X SKU Coprocessor Case Temperature (T
case) 
vs Power
45.0
55.0
65.0
75.0
85.0
95.0
105.0
0
50
100
150
200
Temperature (
o
C)
Intel® Xeon Phi™ Coprocessor Si Power (W)
T
case
D
C
A
B
<95°C