GENERAL DATA 
 
2-3 
 
 
2.1.2.  WALL TYPE (RAK-18QPA/25QPA/35QPA/50QPA) 
INDOOR 
Unit 
RAK-18QPA 
RAK-25QPA 
RAK-35QPA 
RAK-50QPA 
Nominal capacity adjustable 
  
1,20 ← 1,80 
Nominal Cooling capacity (min - max) 
kW 
1.8 (1.0-2.5) 
2.5 (1.0-3.1) 
3.5 (1.0-4.0) 
5.0 (0.9-5.2) 
Cooling sensible capacity 
kW 
Nominal Heating capacity (min - max) 
kW 
2.5 (1.10-3.20) 
3.4 (1.1-4.4) 
4.2 (1.1-5.0) 
6.5 (0.9-8.1) 
Noise level cooling (sound pressure) 
 (SL / L / M / H) 
dB(A) 
20/26/30/35 
20/26/32/38 
25/29/35/41 
27/31/39/47 
Noise level heating (sound pressure) 
 (SL / L / M / H) 
dB(A) 
23/27/33/36 
23/27/33/39 
26/30/35/41 
27/31/39/47 
Noise level (sound power) 
dB(A) 
56 
57 
57 
60 
Air flow cooling mode (SL / L / M / H) 
m
3
/h 
240/300/402/480  288/360/420/510  240/360/480/606 300/408/540/780 
Air flow heating mode (SL / L / M / H) 
m
3
/h 
240/348/450/540  288/420/480/570  240/420/510/690 330/408/570/810 
Fan Motor 
35 
35 
35 
35 
Drain pump pressure lift 
cm 
Static pressure (SL / L / M / H)  
(nominal conditions SP 00) 
Pa 
Dehumidification 
l/h 
1.2 
1.4 
1.6 
2.8 
Included drain pump 
 
no 
no 
no 
No 
Max. height available for drain pump  
(RAD/RAI only) 
 
no 
no 
no 
No 
Dimensions (H x W x D) 
mm 
300x790x230 
300x790x230 
300x790x230 
300x790x230 
Panel dimensions (H x W x D) 
mm 
Weight 
kg 
10.0 
10.0 
10.0 
10.0 
Colour (Munsell Code) 
 
Clear White (*ZLL159M) 
Condensate Drain 
mm 
φ16
 
φ16
 
φ16
 
φ16
 
Panel weight 
kg 
Panel reference 
 
Color of the panel (RAL) 
 
Running current 
2.57-2.36 /  
3.17-2.90 
3.44-3.16 /  
3.17-3.66 
5.00-4.59 /  
4.96-4.55 
8.14-7.50 /  
9.00-8.30 
Power supply 
 
35 V DC from 
outdoor unit 
35 V DC from 
outdoor unit 
35 V DC from 
outdoor unit 
35 V DC from 
outdoor unit 
Cable section 
mm² 
N/A 
N/A 
N/A 
N/A 
Piping diameter (Liq / Gas) 
  
1/4" / 3/8" 
1/4" / 3/8" 
1/4" / 3/8" 
1/4" / 1/2" 
Drain diameter (ext) 
mm 
φ16 
φ16 
φ16 
φ16 
Remote control (standard/optional)  * 
 
RAR-5E1/ 
SPX-RCDB 
RAR-5E1/  
SPX-RCDB
 
RAR-5E1/  
SPX-RCDB
 
RAR-5E1/  
SPX-RCDB
 
Filter 
 
 
 
 
 
ACL Filter 
 
Wasabi 
Wasabi 
Wasabi 
Wasabi 
Dimensions (H x W x D) 
mm 
48x243x5 
48x243x5 
48x243x5 
48x243x5 
Pre-filter (Standard / Optional) 
 
Washable / 
Stainless 
Washable / 
Stainless 
Washable / 
Stainless 
Washable / 
Stainless 
*
more information regarding remote control can be found in Chapter 9 
 
NOTE: 
1.  The nominal cooling and heating capacity is the 
combined capacity of the HITACHI standard split 
system, and are based on the ISO 5151.
 
 
2.  The Sound Pressure Level is based on the following 
conditions:  
0.8 meter beneath indoor height center 
1 meter from Discharge grille 
The above data was measured in an anechoic 
chamber so that reflected sound should be taken into 
consideration when installing the unit. 
 
Operation Conditions 
Cooling 
Heating 
 
Indoor Air Inlet Temperature
 
dB 
27.0 °C
 
20.0 °C 
 
WB 
19.0 °C
 
 
 
Outdoor Air Inlet Temperature
 
dB 
35.0 °C
 
7.0 °C
 
 
WB 
 
6.0 °C 
 
Piping Length: 5.0 meters; Piping Lift: 0 meter 