Hitachi RAF-35RPA RAF35RPA User Manual

Product codes
RAF35RPA
Page of 706
 
GENERAL DATA 
2-4
 
 
2.1.3. 
CEILING CASSETE (RAI-25RPA/35RPA/50RPA)
 
INDOOR 
Unit 
RAI-25RPA 
RAI-35RPA 
RAI-50RPA 
RAI-ECPP 
Nominal capacity adjustable  
  
 
Nominal Cooling capacity (min - max) 
kW 
2.5 (0.9-3.0) 
3.5 (0.9-4.0) 
5.0 (0.9-5.2) 
 
Cooling sensible capacity  
kW 
2.0 
2.9 
3.8 
 
Nominal Heating capacity (min - max) 
kW 
3.5 (0.9-5.0) 
4.8 (0.9-6.6) 
6.2 (0.9-7.6) 
 
Noise level cooling (sound pressure)  
(SL / L / M / H) 
dB(A) 
25/29/32/35 
26/29/34/39 
29/32/35/43 
 
Noise level heating (sound pressure)  
(SL / L / M / H) 
dB(A) 
27/30/33/36 
29/32/36/40 
30/32/36/43 
 
Noise level (sound power) 
dB(A) 
50 
58 
58 
 
Air flow cooling mode (SL / L / M / H) 
m
3
/h 
330/360/420/480 
390/420/510/570  390/450/510/630 
 
Air flow heating mode (SL / L / M / H)  
m
3
/h 
390/420/480/540 
450/480/510/660  450/510/540/690 
 
Fan Motor 
25 
25 
25 
 
Drain pump pressure lift 
cm 
11.5 
11.5 
11.5 
 
Static pressure (SL / L / M / H)  
(nominal conditions SP 00) 
Pa 
 
Dehumidification 
l/h 
1.4 
1.8 
2.0 
 
Included drain pump 
 
yes 
yes 
yes 
 
Max. height available for drain pump  
(RAD/RAI only) 
 
115 
115 
115 
 
Dimensions (H x W x D) 
mm 
285x580x580 
285x580x580 
285x580x580 
32x650x650 
Panel dimensions (H x W x D) 
mm 
32x650x650 
32x650x650 
32x650x650 
 
Weight 
kg 
20.0 
20.0 
20.0 
 
Colour (Munsell Code) 
 
Optional panel (RAI-ECPP) 
Pure White 
(N9.25) 
Condensate Drain 
mm 
φ16
 
φ16
 
φ16
 
 
Panel weight 
kg 
4.0 
4.0 
4.0 
 
Panel reference 
 
RAI-ECPP 
RAI-ECPP 
RAI-ECPP 
 
Color of the panel (RAL) 
 
RAL 9010 
RAL 9010 
RAL 9010 
 
Running current 
3.2~2.93 / 
4.3~3.96 
5.05~4.63 / 
6.24~5.72 
9.1~8.37 / 
9.87~9.05 
 
Power supply 
 
35 V DC from 
outdoor unit 
35 V DC from 
outdoor unit 
35 V DC from 
outdoor unit 
 
Cable section 
mm² 
N/A 
N/A 
N/A 
 
Piping diameter (Liq / Gas) 
  
1/4" / 3/8" 
1/4" / 3/8" 
1/4" / 1/2" 
 
Drain diameter (ext) 
mm 
φ16 
φ16 
φ16 
 
Remote control (standard/optional)  * 
 
RAR-5E2/ 
SPX-RCDB 
RAR-5E2/  
SPX-RCDB
 
RAR-5E2/  
SPX-RCDB
 
 
Filter 
 
 
 
 
 
ACL Filter 
 
Wasabi (Optional)  Wasabi (Optional)
 
Wasabi (Optional)
 
 
Dimensions (H x W x D) 
mm 
35x270x5 
35x270x5
 
35x270x5
 
 
Pre-filter (Standard / Optional) 
 
Washable/- 
Washable/- 
Washable/- 
 
*
more information regarding remote control can be found in Chapter 9 
NOTE: 
1.  The nominal cooling and heating capacity is the 
combined capacity of the HITACHI standard split 
system, and are based on the ISO 5151.
 
 
2.  The Sound Pressure Level is based on the following 
conditions:  
0.8 meter beneath indoor height center 
1.5 meter from Discharge grille 
The above data was measured in an anechoic 
chamber so that reflected sound should be taken into 
consideration when installing the unit. 
 
Operation Conditions 
Cooling 
Heating 
 
Indoor Air Inlet Temperature
 
dB 
27.0 °C
 
20.0 °C 
 
WB 
19.0 °C
 
 
 
Outdoor Air Inlet Temperature
 
dB 
35.0 °C
 
7.0 °C
 
 
WB 
 
6.0 °C 
 
Piping Length: 5.0 meters; Piping Lift: 0 meter 