Ziehl MINIPAN 350 DC Digital measuring and switching device MINIPAN 350 DC 1 mV - 500 V/DC / 1 mA - 1 A D 890110.CO Data Sheet

Product codes
D 890110.CO
Page of 12
date / name ) : 08.10.07 WL / Fu 
Z. Nr.: 12180-0701-01 
Page  5  of  12 
Type: Minipan 350 V 
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: info@ziehl.de 
Setting of Parameters: 
Decimal point behind last digit: 
 
off 
= display mode (measured values)  
 
on 
= menu mode, select the menu items 
  blinking 
= parameter setting mode
  
 
Display Mode 
Display of actual measured value. 
Function buttons Up/Down 
 
Push short  
 
Change to menu mode, selection of menu item 
 
Push for > 2 s   
Display of stored MIN- or MAX- values  
Function of button Set /Reset 
 
Push short  
no function 
 
 
Push for > 2 s 
Reset of MIN- or MAX-value (with Min- or Max-button pushed  
 
 
simultaneously) 
 
Push for > 10 s 
Display of software-version 
 
Menu Mode 
(Decimal point behind last digit ON) 
Selection of the menu items for changing the parameters.  
Function buttons Up/Down 
 
Push short 
Selection of menu item; Change into display mode 
Function Taste Set/Reset 
 
 
Push short 
 
Change into parameter setting mode 
 
Parameter setting mode (Decimal point behind the last digit FLASHES) 
Function buttons Up/Down 
Push short/long  
Adjustment of parameter value  (slow/fast) 
Function button Set/Reset 
  Push short  
Storage of setting and choice of next parameter.  
 
 
 
 
 
 
Change into menu mode after the last parameter 
 
Parametrizing of Input / Measuring Range 
Select menu item with Up/Down until display InPU and measuring range alternate. 
Change into parametrizing mode with Set and select measuring range with Up/Down. 
Confirm and change to next menu with Set. 
When changing measuring range parameters for scaling the display are set to: 
InLo = 0%, InHi = 100 % of measuring range, diLi = 0, diHi = 5000 und dp = 0000. 
 
Scaling the Display 
Select menu item with Up/Down until display ScAL and mode (Auto or USEr) alternate. 
Change into parametrizing mode with Set and select mode with Up/Down.  
Auto:  Display = measured signal without scaling. 
USEr:  Range of input-signal and range of display can be set by the user. The range of the 
input-signal must be within the measuring range.