D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN
EN | 45
Bosch Security Systems | 1/04 | 47775E
A# Fail to Close
Default:
No
Selection:
Yes or No
Yes
Fail to Close Report occurs for this area if the
area was not armed when the Closing
Window stop time occurred.
Note:
An exit delay time must be programmed in Exit
Dly Time.
No
Fail to Close Report is not sent for this area.
Note:
If 
Auto Close is programmed Yes, a Fail to
Close Report is sent because it occurs when the
Closing Window stop time occurred.
If 
Disable O/C in Window is Yes, the Fail
to Close Report is followed by Closing Late or
F(orce) Close Late.
Determines if a Fail to Close Report is sent for this
area. Use to determine if a user failed to arm the
area before the Closing Window expires. Normal
Opening and Closing Reports do not need to be
programmed to use this feature.
A# Restrictd O/C
Default:
No
Selection:
Yes or No
Yes
Restrict Opening and Closing Reports for this
area. 
A# Area O/C
 must be programmed
Yes to generate Restricted Opening and
Closing Reports.
Note:
If a passcode is not required for arming or
disarming and this item is Yes, the area only
sends Restricted Opening and Closing Reports.
In this case, Restricted Reports are sent without
User ID.
Opening/Closing Window does not affect this
report. Windows do not prevent Restricted
Opening and Closing Reports from being
sent. Early or late designations are NOT
added to Opening/Closing Reports when they
are sent according to the rules for Restricted
Opening/Closing Reports.
No
Do not Restrict Opening and Closing Reports
for this area.
Regardless of programming in Authority
Levels 
L## Restricted O/C
, reports are not
restricted in this area when this item is
programmed No.
Note:
Was Force Armed and Forced Close Events can
still be sent to the central station if enabled in
Routing when force arming the system.
This item determines if this area can restrict
Opening and Closing Report activity.
A Restricted Opening Report refers to the control
panel sending an Area Opening Report only when
the area is disarmed after a non-fire alarm.
A Restricted Closing Report refers to the control
panel sending an Area Closing Report only when
the area was master armed with Controlled points
that were faulted during the arming sequence. The
sequence of reports generated by a restricted closing
is: Was Force Armed, Forced Point, Forced Close,
and Closing Report.