CC# A1[through A8] in Scope
Default:
See preceding important note
Selection:
Yes or No
Yes
Include this area in the scope of this
command center.
No
Do not include this area in the scope of
this command center.
Determines whether any of the eight areas (Area 1 to
Area 8) and Doors (Door 1 to Door 8) are included
in the scope of this command center for viewing
status, arming or disarming, and controlling doors
from the command center.
CC# Entr Key Rly
Default:
Blank
Selection:
1 to 128, A, B, C, and Blank
Blank
The [ENTER] key is not used to cycle
a relay.
1 to 128,
A, B, C
Assign the relay number that activates
when [ENTER] is pressed at this
command center after the user enters a
valid passcode.
Enter Key Relay: Program the relay number that
momentarily activates for 10 seconds when a user
enters a valid passcode and presses the [ENTER]
key on the command center. Two events are
generated when this function is used: RELAY ###
SET with User ID, and RELAY ### RESET
without User ID.
When programmed to activate a relay, the
[ENTER] key cannot be used for any other
function.
Relays used for this function must not be
shared with any other point, sensor reset,
control panel, or bell functions. This can
cause erroneous relay operation.
1.
 
Entering a valid code and pressing
[ENTER] silences a bell if one is
ringing.
2.
 
Use this function for a low-level
access control strike on a door. This
does not shunt a point.
3.
 
This action is logged as two events,
Relay Set and Relay Reset.
CC# Entr Cycl Dr
Default:
No
Selection:
Yes or No
Yes
The [ENTER] key is used to cycle the
door programmed for CC Assign
Door.
No
The [ENTER] key is not used to cycle
the door.
Enter Key Cycle Door: Program this prompt as
Yes to initiate the door cycle sequence (this includes
shunting the point assigned to the door) for the door
number programmed in 
CC Assign Door
 when a
user enters a valid passcode and presses [ENTER].
ACCESS GRANTED
 prints on the local printer and at
the central station receiver, if programmed.
The service passcode cannot be used for
the CC# Entr Cycl Dr application.
When programmed to activate a relay, the
[ENTER] key cannot be used for any other
function.
Relays used for this function must not be
shared with any other point, sensor reset,
control panel or bell functions. This can
cause erroneous relay operation.
0101
0101
0101
1.
 
The door does not cycle if Entr Key
Rly
 is programmed.
2.
 
9210 NOT READY
 appears at this
command center when you press
[ENTER] if the D9210B is not
programmed with a D# Entry Area (in
the RADAXS handler) or if CC Assign
Door does not have a door number