Testing Your System 
EN | 29 
 
 
Bosch Security Systems | 6/05 | 4998154961B 
 
10.4  Fire Walk Test 
This test confirms that smoke detectors report alarms to the keypads. The Fire Walk Test tests all fire zones, 
including verified fire and waterflow.  
This test requires you to manually alarm each zone. 
If programmed, a Fire Walt Test report is sent to the central station at the start of a Fire Walk Test. Fire alarm 
reports are not sent to the central station during the Fire Walk Test. A Fire Walk Test restoral is sent upon 
completion of the Fire Walk Test.  
The Fire Walk Test runs for 20 minutes once it is started. The test time is extended to 20 minutes every time you 
test another zone.  
When you test a fire zone, any output programmed to follow that zone is activated for 5 seconds. 
 
Table 28: Fire Walk Test 
 
 
 
 
Type of Test  
Command Sequence 
What Happens 
What To Do 
Fire Walk Test 
[PIN][#][9][1] 
 
•  “Fire Test” is displayed followed by the number 
of any zones that are untested. * 
•  The LEDs of any untested zones flash. ** 
•  “Fire Testing” is displayed followed by the 
number of the zone currently being tested. * 
•  The LED for the zone currently being tested 
turns on steady. ** 
•  As each zone is tested, the “Fire Test” message 
appears followed by the remaining untested 
zones. * 
•  As each zone is tested, its LED turns off. ** 
•  Test each zone as 
instructed by your 
installing company. 
•  Exit the Fire Walk Test 
using [PIN][#]. 
* Text keypad only 
** LED keypad only 
 
 
A Fire Walk Test prevents the system from sending any Fire Reports during the test.