GAS CONVERSIONS
IMPORTANT: Gas conversions from Natural gas to LP gas must 
be done by a qualified installer.
LP Gas Conversion
1. Turn the manual shutoff valve to the closed position.
2. Unplug cooktop or disconnect power.
To Convert Gas Pressure Regulator
1. Remove the access cap by using a wrench, turning the 
access cap counterclockwise.
2. Remove spring retainer from the cap by pushing against the 
flat side of the spring retainer. Look at the spring retainer to 
locate the “NAT” or “LP” position. Turn over the spring 
retainer so the “LP” is showing on the bottom. Snap the 
spring retainer back into the cap. Reinstall the cap onto the 
regulator.
3. Test the gas pressure regulator and gas supply line.
The regulator must be checked at a minimum 1" (2.5 cm) 
water column above the set pressure. The inlet pressure to 
the regulator should be as follows for operation and checking 
the regulator setting:
LP Gas:
Minimum pressure 11" (27.9 cm) WCP 
Maximum pressure 14" (35.5 cm) WCP
Gas Supply Pressure Testing
Gas supply pressure for testing regulator must be at least 
1" water column pressure above the manifold pressure 
shown on the model/serial rating plate.
Line pressure testing above ½ psi gauge (14" WCP)
The cooktop and its individual shutoff valve must be 
disconnected from the gas supply piping system during any 
pressure testing of that system at test pressures in excess of 
½ psi (3.5 kPa).
Line pressure testing at ½ psi gauge (14" WCP) or lower
The cooktop must be isolated from the gas supply piping 
system by closing its individual manual shutoff valve during 
any pressure testing of the gas supply piping system at test 
pressures equal to or less than ½ psi (3.5 kPa).
A. To cooktop
B. Shutoff valve (closed position)
C. Gas supply line
WARNING
Explosion Hazard
Use a new CSA International approved gas supply line.
Install a shut-off valve.
Securely tighten all gas connections.
If connected to LP, have a qualified person make sure 
gas pressure does not exceed 14" (36 cm) water 
column. 
Examples of a qualified person include: 
licensed heating personnel, 
authorized gas company personnel, and
authorized service personnel.
Failure to do so can result in death, explosion, or fire.
A
B
C
A. Access cap
B. Gasket
C. Gas pressure regulator
D. LP position
E. NAT position
A
B
C
D
E