Load Considerations 
Series N5700 User’s Guide 
29 
If remotely located distribution terminals are used, as shown in the 
following figure, the power supply output terminals should be 
connected to the remote distribution terminals by a pair of twisted 
and/or shielded wires. Connect each load to the distribution 
terminals separately. Remote voltage sensing is recommended under 
these circumstances. Sense either at the remote distribution 
terminals or, if one load is more sensitive than the others, directly at 
the critical load. 
Output Noise and Impedance Effects 
To minimize the noise pickup or radiation, the load wires and remote 
sense wires should be twisted-pairs to the shortest possible length. 
Shielding of sense leads may be necessary in high noise 
environments. Where shielding is used, connect the shield to the 
chassis via a rear panel ground screw. Even if noise is not a concern, 
the load and remote sense wires should be twisted-pairs to reduce 
coupling, which might impact the stability of power supply. The sense 
leads should be separated from the power leads. 
Twisting the load wires reduces the parasitic inductance of the cable, 
which could produce high frequency voltage spikes at the load and 
the output because of current variation in the load itself. 
The impedance introduced between the power supply output and the 
load could make the ripple and noise at the load worse than the noise 
at the power supply rear panel output. Additional filtering with 
bypass capacitors at the load terminals may be required to bypass the 
high frequency load current. 
Inductive Loads 
Inductive loads can produce voltage spikes that may be harmful to 
the power supply. A diode should be connected across the output. 
The diode voltage and current rating should be greater than the 
power supply maximum output voltage and current rating. Connect 
the cathode to the positive output and the anode to the negative 
output of the power supply. 
Where positive load transients such as back EMF from a motor may 
occur, connect a surge suppressor across the output to protect the 
power supply. The breakdown voltage rating of the suppressor must 
be approximately 10% higher than the maximum output voltage of the 
power supply. 
-
-
Rem.sense
Local sense
ocal sense
Rem.sense
+L
+
Distribution terminal
+V
+V
-V
-V
Load#1
+
Load#3
+
Load#2
+
Power 
Supply