section 3 – Maintenance
recreational vehicle generator
Figure 3.3 – Cleaning Air Intake
USTC
3.5    checkIng the engIne spark 
plug
Clean  the  spark  plug  and  reset  the  spark  plug  gap 
every 100 hours of operation.
1.  Clean the area around the base of the spark plug 
to keep dirt and debris out of the engine. Remove 
the spark plug and check the condition. Replace 
the  spark  plug  if  worn  or  if  reuse  is  question-
able.
2.  Clean spark plug by scraping or washing using a 
wire brush and commercial solvent. Do not blast 
the spark plug to clean.
3.  Check  the  spark  plug  gap  using  a  wire  feeler 
gauge.  Adjust  the  gap  to  0.030  inch  (0.76  mm)  
by  carefully  bending  the  ground  electrode  
(Figure 3.4).
Figure 3.4 – Setting the Spark Plug Gap
 
  Sparking can occur if the wire terminal does 
not fit firmly on the spark plug terminal end. If 
necessary, re-form the wire terminal to obtain 
a tight fit.
3.6   clean spark arrestor
The  engine  exhaust  muffler  has  a  spark  arrestor 
screen. Inspect and clean the screen every 50 hours 
of operation or once each year, whichever comes first 
(Figure 3.5).
NOTE:
If  using  the  generator  on  any  forest-covered, 
brush-covered or grass-covered unimproved land, 
it must equipped with a spark arrestor. The spark 
arrestor must be maintained in good condition by 
the owner/operator.
Clean and inspect the spark arrestor as follows:
•   Remove the screen retaining bracket by removing 
the screw.
•   Slide  the  spark  arrestor  screen  out  from  the  tail 
pipe.
•   Inspect  screen  and  replace  if  torn,  perforated  or 
otherwise  damaged.  DO  NOT  USE  a  defective 
screen. If screen is not damaged, clean it with com-
mercial solvent.
•  Replace the screen and the retaining bracket.
Figure 3.5 - Spark Arrestor
RETAINING 
SCREW P/N 056892
SPARK ARRRESTOR
SCREEN P/N 089680
TAILPIPE
P/N 0E0683
3.7  cleanIng the generator
Keep the generator set as clean and dry as possible.  
Protect the unit against excessive dust, dirt, corrosive 
vapors,  road  splash,  etc.  Permitting  dirt  and  mois-
ture  to  accumulate  on  generator  windings  will  have 
an adverse effect on the insulation resistance of those 
windings.
When moisture is allowed to remain in contact with 
windings,  some  of  the  moisture  will  be  retained  in 
voids  and  cracks  in  the  insulation.  This  causes  a 
reduced  insulation  resistance  and  will  eventually 
cause problems. Dirt will make the problem worse, 
since  dirt  tends  to  hold  moisture  in  contact  with 
windings. Salt (as from sea air) also will worsen the 
problem since it tends to absorb moisture from the 
air. Salt and moisture, when combined, form a good 
electrical  conductor  which  can  be  damaging  to  the 
generator windings.