Benning IT 120 B 044102 Manual De Usuario

Los códigos de productos
044102
Descargar
Página de 80
45
5.9  Resistance to earth (R
E
) ( BENNING IT 120 B only)
The BENNING IT 120 B allows resistance to earth measurement using 3-wire measuring me-
thod (earthing set). Consider the following instructions when performing resistance to earth 
measurement:
-   The probe (S) is positioned between the earth electrode (E) and auxiliary earth electrode (H) in 
the earth reference plane (see figure 5.45).
-   The distance from the earth electrode (E) to the auxiliary earth electrode (H) must be at least 5 
times the depth or length of the earthing electrode rod (see fig. 5.45).
How to perform resistance to earth measurement:
Step 1 
Select R
E
, ERDE/ EARTH function with the function selector switch. The following menu 
is displayed: 
Fig. 5.44: Earth resistance measurement menu
 
 
Connect the measuring cables to the BENNING IT 120 B.
Step 2 
Set the following measuring parameters and limit values:
 
 
 High limit resistance value
Step 3
 Follow the connection diagram shown in figure 5.45 to perform resistance to earth mea-
surement. Use the Help function if necessary. 
 
 
(Measuring cables: H = black, S = green, E = blue)
Fig. 5.45: Measurement with the earthing set – 20 m
Step 4  
Check the displayed warnings and online voltage/terminal monitor before starting the 
measurement. If OK, press the TEST key. After performing, the measurement results 
appear on the display together with the PASS/FAIL indication (if applicable).
Fig. 5.46: Example of resistance to earth measurement results