Displayed results: 
R:  
Resistance to earth
R
C: 
 
Auxiliary earth electrode resistance
R
P: 
 
Probe resistance
Save displayed results for documentation purposes. Refer to chapter 6.1 for further information on 
setting functions and saving of measurement results.
Note:
-   If the voltage between the test terminals H and E is higher than 30 V the earth measurement 
will not be performed.
-   If the value for the auxiliary earth electrode or the probe resistance is too high (100*RE or > 
50 kΩ), the respective warning symbol will be displayed in the message field. The measure-
ment results may be affected!
-   If a noise voltage higher than approx. 5 V is present between the H and E or S test terminals, a 
warning symbol “
” will be displayed in the message field. The measurement results may be
affected!
5.10  TRUE RMS current (A~) (BENNING IT 120 B only)
This function enables measuring of AC currents in a wide range from 0.5 mA to 20 A. Load cur-
rents can be measured quickly and reliably. The TRUE RMS functions guarantees a correct test 
result even for non-sinusoidal signals. The current clamp adapter BENNING CC 2 can be used for 
measuring load currents between 0.5 A and 20 A.
How to perform TRUE RMS current measurement:
Step 1
 
Select A~ TRUE RMS (current) function with the function selector switch. The following 
menu is displayed:
Fig. 5.47: TRUE RMS current measurement menu
 
 
Connect the current clamp to the BENNING IT 120 B.
Step 2
  Follow the connection diagram shown in fig. 5.48 to perform the TRUE RMS current
measurement. Use the Help function if necessary.