Service Menu Parameters
159
Liebert
®
iCOM
®
S628 Supply/Return Sensor—Applies to both supply and return sensors; adjusts the supply
temperature reading from the actual sensor to compensate for any sensor error or to match other
sensors in the room.
S629 Calibrated Supply/Return Sensor—Applies to both supply and return sensors. Liebert
S629 Calibrated Supply/Return Sensor—Applies to both supply and return sensors. Liebert
iCOM will automatically detect the sensor connected and update the parameter name to reflect the
sensor location; shows the adjusted temperature value of the supply sensor. This value is the actual
sensor reading (+ or -) the offset Supply/Return Sensor.
S630 Offset Outdoor Temperature/Offset Optional Sensor C1T—Applies to both outdoor sensor
S630 Offset Outdoor Temperature/Offset Optional Sensor C1T—Applies to both outdoor sensor
and optional Sensor C. Liebert iCOM will automatically detect the sensor connected and update the
parameter name to reflect the sensor location. Adjusts the outdoor temperature reading or sensor C
from the actual sensor reading to compensate for any sensor error or to match other sensors.
S631 Calibrated Outdoor Temperature/Calibrated Optional Sensor C1T—Applies to both
S631 Calibrated Outdoor Temperature/Calibrated Optional Sensor C1T—Applies to both
outdoor sensor and optional Sensor C. The Liebert iCOM will automatically detect the sensor
connected and update the parameter name to reflect the sensor location; shows the adjusted
temperature value of the outdoor temperature or sensor C1T. This value is the actual sensor reading
(+ or -) the “Offset Outdoor Temperature”.
S632 Offset Outdoor Humidity/ Offset Optional Sensor C2H—Applies to both outdoor sensor
S632 Offset Outdoor Humidity/ Offset Optional Sensor C2H—Applies to both outdoor sensor
and optional Sensor C. The Liebert iCOM will automatically detect the sensor connected and update
the parameter name to reflect the sensor location; adjusts the outdoor or sensor C2H humidity
reading from the actual sensor reading to compensate for any sensor error or to match other sensors.
S633 Calibrated Outdoor Humidity/ Calibrated Optional Sensor C2H—Applies to both
S633 Calibrated Outdoor Humidity/ Calibrated Optional Sensor C2H—Applies to both
outdoor sensor and optional Sensor C. The Liebert iCOM will automatically detect the sensor
connected and update the parameter name to reflect the sensor location; shows the adjusted humidity
value of the outdoor or C2H humidity sensor. This value is the actual sensor reading (+ or -) the
“Offset Outdoor Humidity” or “Offset Optional Sensor C1T” or “Offset Optional Sensor C2H.”
S63A Optional Sensor C2T—Shows the adjusted temperature value of the sensor C. This value is
S63A Optional Sensor C2T—Shows the adjusted temperature value of the sensor C. This value is
the actual sensor reading (+ or -) the “Calibrated Optional Sensor C2T”.
S63B Calibrated Optional Sensor C2T—Adjusts the optional sensor C2T reading from the actual
S63B Calibrated Optional Sensor C2T—Adjusts the optional sensor C2T reading from the actual
sensor reading to compensate for any sensor error or to match other sensors.
Figure 152
Sensor calibration/setup screen, page 4 of 12