Emerson Liebert iCOM Manual De Usuario

Descargar
Página de 196
Service Menu Parameters
Liebert
®
 iCOM
®
160
Figure 153
Sensor calibration/setup screen, page 5 of 12
Each unit can be equipped with a total of 20 rack sensor readings or ten 2T temperature sensor 
modules. These menus permit temperature sensor calibration by entering a negative or positive 
offset.
The calibrated reading is displayed in the far right column. If a value does not appear in the far right 
column, then the sensor is either not set up correctly or is not connected.
Figure 154
Sensor calibration/setup screen, page 6 of 12
S657 DP Transducer is Connected to—Sets the analog input that will be used for the differential 
pressure transducer. This parameter is selectable from None, Ana In 1, Ana In 2, Ana In 3 and 
Ana In  4. The factory default is none.
S658 DP Transducer is Setup in—Sets the unit of measure that will be used for the differential 
pressure transducer. This parameter is selectable in inWC or PA. The factory default is PA.
S659 DP Transducer Low—Sets the unit of measure that will be used for the low differential 
pressure transducer. This parameter is selectable from 0-9.999 inWC. The factory default is 0.000 
inWC.
S660 DP Transducer High—Sets the unit of measure that will be used for the high differential 
pressure transducer. This parameter is selectable from 0-9.999 inWC. The factory default is 2.005 
inWC.