Service Menu Parameters
161
Liebert
®
iCOM
®
S661 Number of EC Fans—Sets the unit of number of EC fans. This parameter is selectable
between 1 and 5. The factory default is 3.
S662 Inlet Ring K-Value—Sets the inlet ring K-Value. This parameter is selectable between 1 and
S662 Inlet Ring K-Value—Sets the inlet ring K-Value. This parameter is selectable between 1 and
999. The factory default is 480.
S664 Results:—Read-only string that describes S665 through S668.
S665 DP Transducer Low—Shows the status of the low differential pressure transducer in both
S664 Results:—Read-only string that describes S665 through S668.
S665 DP Transducer Low—Shows the status of the low differential pressure transducer in both
inWC and Pa after it’s setup at S659.
S666 DP Transducer High—Shows the status of the high differential pressure transducer in both
S666 DP Transducer High—Shows the status of the high differential pressure transducer in both
inWC and Pa after it's setup at S660.
S667 Actual DP Signal—Shows the actual differential pressure transducer percentage.
S668 Calculated Airflow—Shows the calculated airflow based on the low, high, number of EC fans
S667 Actual DP Signal—Shows the actual differential pressure transducer percentage.
S668 Calculated Airflow—Shows the calculated airflow based on the low, high, number of EC fans
and the Inlet Ring K-Value settings.
Figure 155
Sensor calibration/setup screen, pages 7 and 8 of 12
Up to four static pressure transducers may be programmed on Screens 7 and 8. Four static pressure
transducers are shows in Figure 155 for simplicity. Transducer information will be hidden if a device
has not been configured on SP# Reading from.
SP# Reading from—Sets the analog input that will be used for the static pressure transducer. This
SP# Reading from—Sets the analog input that will be used for the static pressure transducer. This
parameter is selectable from None, Ana In 1, Ana In 2, Ana In 3 and Ana In 4. The user may also
choose to select Network. This setting allows the unit to operate based on a shared static pressure
value across the U2U network. This setting does not required a static pressure transducer connection
at the unit. The default is none.
SP# Unit of Measurement—Sets the unit of measure that will be used for the static pressure
SP# Unit of Measurement—Sets the unit of measure that will be used for the static pressure
transducer. This parameter is selectable in inWC or PA. The default is PA.
SP# Transducer Low—Calibrates the static pressure transducer; sets the value displayed at the
SP# Transducer Low—Calibrates the static pressure transducer; sets the value displayed at the
starting point of the analog input signal. This parameter is selectable from 0-9.999 inWC or
0.0-2491.0 Pa. The default is 0.000 inWC or 0.0 Pa.
SP# Transducer High—Calibrates the static pressure transducer; sets the maximum value
SP# Transducer High—Calibrates the static pressure transducer; sets the maximum value
displayed, or end point, of the analog input. This parameter is selectable from 0-9.999 inWC or
0.0-2491.0 Pa. The default is 2.005 inWC or 500.0 Pa.
Actual SP# Signal—Shows the current static pressure based on low and high settings.
Aggregation Method—Up to four different analog inputs can be configured for static pressure. The
Actual SP# Signal—Shows the current static pressure based on low and high settings.
Aggregation Method—Up to four different analog inputs can be configured for static pressure. The
aggregation method defines if the resulting pressure is the Average, Maximum or the Minimum of all
connected sensors.
Aggr. Unit Static—Displays the unit static pressure based on the Aggregation Method setting.
Network Static Pressure—Displays the maximum or average U2U network static pressure of all
Aggr. Unit Static—Displays the unit static pressure based on the Aggregation Method setting.
Network Static Pressure—Displays the maximum or average U2U network static pressure of all
devices connected in the group. The maximum or average reading is based on the value programmed
in Service Menus>System / Setpoints, S197 SP Teamwork / Network Mode.