Emerson Liebert iCOM Manual De Usuario
Service Menu Parameters
Liebert
®
iCOM
®
162
Figure 156
Sensor calibration/setup screen, page 9 of 12
S696 FL1 Transducer is Connected to—Sets the analog input and the input range that will be
used with the flow meter. This parameter is selectable from None, Ana In 1, Ana In 2, Ana In 3 and
Ana In 4. The factory default is None. The input range options are 0-5VDC, 0-10VDC, and 4-20mA.
S697 FL2 Transducer is Connected to—Sets the analog input and the input range that will be
S697 FL2 Transducer is Connected to—Sets the analog input and the input range that will be
used with the flow meter. This parameter is selectable from None, Ana In 1, Ana In 2, Ana In 3 and
Ana In 4. The factory default is None. The selectable input range options are 0-5VDC, 0-10VDC, and
4-20mA.
S698 FL Transducer Setup in—Sets the unit of measure for the flow readout. Two options are
S698 FL Transducer Setup in—Sets the unit of measure for the flow readout. Two options are
available, m/s (meter per second) and f/s (feet per second). The factory default is m/s.
S699 FL Transducer Low—Used for calibrating the flow meter. Sets the value displayed at the
S699 FL Transducer Low—Used for calibrating the flow meter. Sets the value displayed at the
starting point of the analog input signal. This parameter is selectable from 0.00 - 9.99 m/s or
0.00 - 32.48 f/s. The factory default is 0.98 f/s or 0.30 m/s.
S6A1 FL Transducer High—Used to calibrate the flow meter. Sets the maximum value displayed,
S6A1 FL Transducer High—Used to calibrate the flow meter. Sets the maximum value displayed,
or end point of the analog input. This parameter is selectable from 0.00 - 9.99 m/s or 0.00 - 32.48 f/s.
The factory default is 16.40 f/s or 5.00 m/s.
S6A2 Internal Pipe Diameter—Sets the inside pipe diameter of pipe where the flow meter is
S6A2 Internal Pipe Diameter—Sets the inside pipe diameter of pipe where the flow meter is
installed. Units of measure include inches and millimeters. This parameter is selectable from
0.39-39.36 in or 10.0-999.9 mm. The factory default is 1.00 in or 25.4 mm.
S6A3 Set Reading to 0 @ Lower—Used to prevent false flow readings when the regulating valve is
S6A3 Set Reading to 0 @ Lower—Used to prevent false flow readings when the regulating valve is
closed or open to a very small percentage. The programmed here is compared to the valve call. If the
valve call is less than the value programmed, the Liebert iCOM will register 0.00 m/s or 0.00 f/s. This
parameter is selectable from 0-50%. The factory default is 5%.
S6A4 Fluid Type / Percent—Sets the fluid type used in the system as a correction factor for
S6A4 Fluid Type / Percent—Sets the fluid type used in the system as a correction factor for
calculating cooling capacity. Three options are available: Water, EGlycol (ethylene glycol), and
PGlycol (propylene glycol). When EGlycol or PGlycol are selected, the percent concentration can be set
in the field to the far right. The factory default fluid type is Water and percent concentration is 0%.
S6A5 Actual FL 1 Signal—Displays the fluid flow rate for flow meter 1 in m/s or ft/s.
S6A6 Actual FL 2 Signal—Displays the fluid flow rate for flow meter 2 in m/s or ft/s.
S6A7 Current Water Flow 1—This parameter displays the fluid flow rate for flow meter 1 in GPM
S6A5 Actual FL 1 Signal—Displays the fluid flow rate for flow meter 1 in m/s or ft/s.
S6A6 Actual FL 2 Signal—Displays the fluid flow rate for flow meter 2 in m/s or ft/s.
S6A7 Current Water Flow 1—This parameter displays the fluid flow rate for flow meter 1 in GPM
(gallons per minute) or l/m (liters per minute).
S6A8 Current Water Flow 2—This parameter displays the fluid flow rate for flow meter 2 in GPM
S6A8 Current Water Flow 2—This parameter displays the fluid flow rate for flow meter 2 in GPM
(gallons per minute) or l/m (liters per minute).