Operation
Liebert
®
 iCOM
®
54
3.7.1 Humidification
Infrared Humidifier
There are two types of infrared humidifiers: small pan (IFS) and large pan (IFL). The operating mode 
of each is similar, however, some of the variables or timings differ because of the size of the pan.
Infrared humidifiers are started at 100% humidification request and stopped at 0%. Infrared 
humidifiers cannot be driven in proportional mode.
An autoflush system automatically controls a water makeup valve to maintain proper levels in the 
infrared humidifier water pan during humidifier operation. If humidification is needed and 15 hours 
have elapsed since the last time the humidifier was on, then the humidifier is not turned On until the 
valve completes an initial fill of the humidifier pan. This pre-fill is about 30 seconds for a small pan 
and 60 seconds for a large pan. The valve continues to fill and flush the pan for about 4-1/2 minutes 
for a small pan or 7-1/2 minutes for a large pan. Pan size is selected based on unit specifications and 
the time is factory-set.
During humidifier operation, with the flush rate set at the default of 150%, the valve is opened 
periodically to add water to the pan (for a small pan, it opens about 45 seconds for every 7 minutes of 
humidifier operation; for a large pan it opens about 80 seconds for every 10 minutes of operation). 
This adds enough water to the pan to cause about a third of the total water used to be flushed out of 
the overflow standpipe in the humidifier pan. This helps to remove solids from the pan. The flush rate 
is adjustable from 110% to 500% in 10% increments. Default is 150%. If the water quality is poor, it 
may be desirable to increase the water flushing action above the normal 150% rate. Also, if the supply 
water pressure is low, the flush rate adjustment can be increased so that a sufficient water level is 
maintained during humidification. The flush rate parameter, Infrared Flush Rate (Service Menu, 
Options Setup), is adjustable from 110%-500% because the fill valve is controlled by time. It uses a 
factory-installed integral float to prevent overfilling if the humidifier drain or condensate pump fails.
External Humidifier Control—Optional
A factory-supplied option may be provided to allow a start-stop command to be sent to the control of a 
remote-mounted humidifier.
Steam Generating Canister Humidifier
The Steam Generating Humidifier has its own separate control board that manages the canister and 
steam rate. Liebert iCOM sends an On-Off command to relay a call for humidification.
3.7.2 Dehumidification
The Dehumidification Enable parameter (Service Menu, Options Setup) allows for enabling/disabling 
the dehumidification function.
A call for dehumidification is calculated in the same way as a cooling request. The components 
(valves, compressors) will follow this dehumidification request as soon as it is higher than the request 
for cooling the hot gas bypass (if equipped) will disengage on the Liebert Challenger 3000
.
Table 8
Parameters for infrared humidifier control
Parameter
IFS Default
IFL Default
Liebert
Challenger
Humidity in Last xx Hours
15 hours
15 hours
15 hours
Fill Time
33 seconds
56 seconds
27 seconds
Humidifier On Time
440 seconds
576 seconds
568 seconds
Flush Rate
150%
150%
150%