Schneider Electric PM5300 Manual De Usuario

Descargar
Página de 120
40
© 2014 Schneider Electric All Rights Reserved
Chapter 4—Front panel display and meter setup
PowerLogic™  PM5300 series user guide
protected prevents unauthorized personnel from accessing certain screens such as the 
diagnostics and reset screens.
If you lose your password, you must return the meter for factory reconfiguration, which 
resets your device to its factory defaults and destroys all logged data.
1. Navigate to Maint > Setup.
2. Enter the setup password (default is “0000”), then press OK.
3. Navigate to HMI > Pass.
4. Move the cursor to point to the parameter you want to modify, then press Edit.
5. Modify the parameter as required, then press OK.
6. Move the cursor to point to the next parameter you want to modify, press Edit
make your changes, then press OK.
7. Press   to exit. Press Yes to save your changes.
Lost password
If you lose your password, contact technical support for instructions on how to return 
your meter for factory reconfiguration.
Global-PMC-Tech-support@schneider-electric.com
(00) + 1 (250) 544-3010
NOTE:
Be sure to include your meter’s serial number in your e-mail or have it readily 
available when calling technical support.
NOTICE
LOST DATA
Record your meter's screen password information in a secure location.
Failure to follow these instructions can result in data loss.
Password setup menu tree
Password setup parameters
Parameter
Values
Description
Setup
0000 - 9999
Sets the password for accessing the meter setup 
screens (Maint > Setup).
Energy Resets
0000 - 9999
Sets the password for resetting the meter’s 
accumulated energy values.
Demand Resets
0000 - 9999
Sets the password for resetting the meter’s 
recorded peak demand values.
Min/Max Resets
0000 - 9999
Sets the password for resetting the meter’s 
recorded minimum and maximum values.
Diagnostics
0000 - 9999
Sets the password for accessing the meter’s 
diagnostics screens.
Maint
Reset
Meter
Comm
Alarm
I/O
I
Clock
Displ
Region
Pass
HMI
Setup