Operating Manual LP 33 Series 30 & 40 kVA 
7.1.5  Restore to normal operation after “total off” 
 
 
NOTE ! 
Make sure the UPS to be status of the activation of “total off”, i. e. Q1 closed, Q2 open 
and the battery fuses F5, F6, F7
 (and eventual external fuses in case of external 
battery) connected. 
 
 
 
 
View of the panel after pressing the button “total off”
• 
All Contactors are open. 
• 
Booster, inverter and Static-Switch shutdown. 
 
LP 33          40kVA 
APPLICAT. SUPPLY OFF 
= 0% 
 
 
 
 
 
1. Reset 
total off”. 
Restore the command “total off” by entering the screen: 
MENU/RESET TOTAL OFF 
 
LED TEST 
RESET TOTAL OFF 
* 
 
 
The load is supplied by the mains through the automatic 
bypass

The booster starts automatically. 
 
The LCD screen must display the status: 
APPLICATION ON BYPASS
 
 
LP 33          40kVA 
APPLICATION ON BYPASS 
= 70% 
 
 
2.  Switch ON the inverter by entering the screen
MENU/COMMAND MENU/INVERTER ON 
 
COMMAND MENU 
INVERTER ON * 
INVERTER OFF 
 
 
The LCD screen must display the status: 
APPLICATION ON UPS
 
 
LP 33          40kVA 
APPLICATION ON UPS 
= 70% 
 
 
END OF PROCEDURE