OPM_LPS_3UO_30K_40K_0US_V010.doc 
Operating Manual LP 33 Series 30 & 40 kVA 
7.1.6  Restore to normal operation after “EPO – Emergency Power Off” 
 
 
NOTE ! 
Make sure the UPS to be status of the activation of “EPO”, i. e. Q1 closed, Q2 open and 
the  battery fuses F5, F6, F7
 (and eventual external fuses in case of external battery) 
connected. 
 
 
View of the panel after pressing the button “EPO”
• 
All Contactors are open. 
• 
Booster, inverter and Static-Switch shutdown. 
 
LP 33          40kVA 
APPLICAT. SUPPLY OFF 
= 0% 
 
 
 
 
1.  Reset the button “EPO”. 
Press Alarm, to reset alarm and buzzer
 
01.01.2005 12:15:45 
NR=255 Status=A588 
4563: 
EMERGENCY OFF 
ACTIVATED 
 
2.  Reset the UPS by entering the screen
MENU/COMMAND MENU/INVERTER OFF 
 
COMMAND MENU 
INVERTER ON * 
INVERTER OFF 
 
 
The load is supplied by the mains through the automatic 
bypass
The booster starts automatically.
 
 
The LCD screen must display the status: 
APPLICATION ON BYPASS
 
 
LP 33          40kVA 
APPLICATION ON BYPASS 
= 70% 
 
 
3.  Switch ON the inverter by entering the screen
MENU/COMMAND MENU/INVERTER ON 
 
COMMAND MENU 
INVERTER ON * 
INVERTER OFF 
 
The  load will be automatically transferred from mains to the 
inverter.
 
 
The LCD screen must display the status: 
APPLICATION ON UPS
 
 
LP 33          40kVA 
APPLICATION ON UPS 
= 70% 
 
 
END OF PROCEDURE