7.2.4 
Shutdown of a single unit in a parallel system 
 
With purpose to separate one unit from the parallel system. 
 
 
1.  Switch OFF the inverter only on this unit entering the screen: 
MENU/COMMAND MENU/INVERTER OFF  
Attention
:  to switch OFF permanently the inverter the key 
Enter must be pressed 2 times
 
COMMAND MENU 
INVERTER ON 
INVERTER OFF * 
 
 
2.  Switch OFF the output switch Q1 (0) only on this unit.
 
 
3.  Perform the command total off only on this unit
 
4.  Remove  the  battery fuses F5, F6, F7 (and eventual external fuses in case of external battery)
only on this unit
 
5.  In order to discharge the DC link capacitors, start once more 
the inverter only on this unit through the screen
MENU/COMMAND MENU/INVERTER ON
 
 
COMMAND MENU 
INVERTER ON * 
INVERTER OFF 
 
 
 
 
Remark: command 
INVERTER ON will be enabled only when 
the inverter voltage of each phase decreases 
below 7 VAC (about 30 seconds). 
 
INVERTER: U1= 
 
7V 
U2=  7V U3=  7V 
Frequency    =    60.0Hz 
Synchronized 
 
 
 
Before proceeding to step 6, check on the display panel that 
the DC link voltage (both polarities) Udcp and Udcn has reached 
the minimum voltage of 5 VDC (about 30 seconds). 
 
Udcp=  5V Udcn= 
5V 
Ubp=0V 
Ubn=0V   O 
Charge level 
=  0% 
Autonomy = 
0min
 
 
6.  Switch OFF the inverter only on this unit entering the screen
MENU/COMMAND MENU/INVERTER OFF 
 
COMMAND MENU 
INVERTER ON 
INVERTER OFF * 
 
 
7.  Switch OFF the mains power only on this unit at the AC input distribution panel. 
 
END OF PROCEDURE 
 
 
 
WARNING ! 
In case the unit should be disconnected and removed from the operating system, the 
operation must be performed by qualified persons. 
If an intermediate unit must be disconnected from a parallel system pay attention 
do not open the control bus: keep the plugs J3 and J4 connected to the board “P16 - 
Connector adapter RPA” (see Section 4.8.4)