GE C11 Manuel D’Utilisation

Page de 98
 
- 81 -
 
Item 
Specifications 
Remarks 
Frequency jump 
control
 
 Jump frequency (3 points) and jump hysteresis width (1 point) can be pre-
set. 
 
Restart after 
momentary 
power failure 
 Drive restarts without causing drive-trip when power supply recovers. 
 
Control
 
PID control 
 PID control function is provided standard. 
 
Enclosure 
(IEC 60529) 
 IP20 
 
Cooling method 
 Natural cooling for 1 HP or less, Fan cooling for 2 HP or more 
 
Running, 
stopped 
 Output frequency, output current, and PID reference value/feedback value 
 
The CRG lamp is on when the capacitor is charged. 
 
Program mode 
 Function code and data code 
 
Tripped 
[Cause of trip by code] 
 OC1 (Overcurrent: during acceleration)  
 OC2 (Overcurrent: during deceleration) 
 OC3 (Overcurrent: while running at constant speed)        
 OU1 (Overvoltage: during acceleration) 
 OU2 (Overvoltage: during deceleration)  
 OU3 (Overvoltage: while running at constant speed) 
 LU (Undervoltage) 
 OH1 (Overheating: Heat sink) 
 OH2 (Overheating: External alarm) 
 OL (Overload: Motor) 
 OLU (Overload: Drive) 
 Er1 (Memory error) 
 Er3 (CPU error) 
 Er6 (Operation error) 
 Er8 (RS485 communication error) 
 Lin (Input phase failure) 
 
Indication
 
Running, 
Tripped 
 Fault history data is stored and indicated for the past four trips. Data is  
retained while power is off.