Item 
Specifications 
Remarks 
Overload 
 Internal electronic thermal overload relay protects drive overload. 
 
Overvoltage 
 Detect the excessive DC link circuit voltage to stop drive. 
 
Overcurrent 
 Detect overcurrent due to overload on drive output side to protect drive 
 
Incoming surge 
 Detect incoming surge voltage between AC power and the earth to protect 
drive. 
 
Undervoltage 
 Detect the DC link circuit undervoltage to stop drive 
 
Overheating 
 Detects the cooling fan fault or abnormal temperature rise of drive to pro-
tect drive. 
 
Short-circuit 
 Detect overcurrent due to short-circuit on drive output side to protect drive.   
Ground fault 
 Detects overcorrect due to ground fault on drive output side to protect drive. 
(Detect at starting) 
 
Motor protection 
 Protect general-purpose motor with electronic thermal overload. 
 
Input phase fail-
ure protection 
(only for 3-phase 
200V series) 
 The drive is protected against phase failure on the input side or over-current 
due to inter-phase imbalance. 
 
Stall prevention 
 Controls frequency to prevent OC trip in case of the output current exceeds 
the limit value during acceleration. 
 Lowers the frequency to hold almost constant torque in case of the output 
current exceeds the limit value during constant speed running. 
 Controls frequency to prevent OU trip in case of the DC link circuit voltage 
exceeds the limit value during deceleration. 
 
Retry 
 “Retry” function can be set for the protective functions OC1 to OC3 and 
OU1 to OU3.(No. of times of retry: 5,  waiting time: 0.5s fixed. 
 
Dielectric 
strength test 
 At 2000Vac for 1 min. between any main circuit terminals and 
ground.(10mA or less) 
 
Protection
 
Megger test 
 At 500Vdc megger test between any main circuit terminals and ground 
(5M
Ω
 or more)