UPS Network Management Card 2 User’s Guide
36
•  For some UPS models, when the state of the outlet group is 
on
 and the UPS is on battery:
Shutdown Immediately, AC Restart
: Turn off the group immediately. After the number of 
seconds configured as 
Reboot Duration
 and 
Power On Delay
, check that AC utility power has 
returned and the UPS can support the minimum return runtime demand, then turn on the group.
Shutdown with Delay, AC Restart
: Turn off the group after the number of seconds configured 
as 
Power Off Delay
. After the number of seconds configured as 
Reboot Duration
 and 
Power 
On Delay
, check that AC utility power has returned and the UPS can support the minimum return 
runtime demand, then turn on the group.
After you select an action, click 
Next>>
 to view a detailed description of the action, including the duration of 
any delays. Click 
Apply
 to commence the action.
Configuration Pages
Configure your shutdowns, your upper and lower limit power settings, your Switched Outlet groups (if 
relevant) and other parameters with these menu options.
Path: UPS > Configuration
This page is not available for all UPS devices.
What are Outlet Groups?
Outlet grouping is available on some UPS models only. To determine whether your UPS model 
supports outlet groups, see your UPS documentation.
The available settings differ based on the UPS model. For detailed information about fields and 
values specific to your UPS model, see the online help.
Main outlet groups . 
Some UPS models provide AC power to one Main Outlet group. The Main Outlet 
group controls the distribution of power to all Switched Outlet groups for the UPS. 
•  If the Main Outlet group is off, the Switched Outlet groups cannot be turned on.
•  If you turn off the Main Outlet group, the UPS turns off the Switched Outlet groups first, then turns off 
the Main Outlet group.
•  To turn on a Switched Outlet group, the UPS must turn on the Main Outlet group first, and then turn on 
the Switched Outlet group.
Switched outlet groups . 
Some UPS models provide power to Switched Outlet groups. Each group can 
perform actions independently of the other groups. By controlling each outlet group remotely, you can start or 
stop models sequentially and also restart locked models.
The way outlet groups turn on and off depends on their configuration and how you turn the UPS on or off:
•  Before you configure the delays for actions described in “Actions (for a single UPS and Synchronized 
Control Groups)” and “Sequencing settings”, when you turn on the UPS output, any outlet group that is 
off turns on by default and applies power to all models attached to the outlets in that group.
•  After you configure the actions and delays, they control how outlet groups turn on and off when you 
turn the UPS on or off from the user interface of the NMC or the display interface at the UPS.