Low-fi re/high-fi re operation – The fuel unit nozzle port 
pressure is factory set at 300 psig.
At high fi re, full pressure (300 psig) is applied at the 
oil nozzle, causing full input.
At low fi re, the by-passing is done inside the fuel unit 
when the by-pass valve operates.
This by-passing of oil reduces the oil pressure at the 
nozzle (to between 125 psig and 175 psig), reducing 
the input.
Model
Fuel Unit Model Number
Gearset Capacity (gph)
CF1400
B2TA-8245
23
CF2300
B2TA-8852
39
Table 3 – Fuel Unit Gearset Capacities
The fuel unit nozzle port pressure 
is factory set at 300 psig. Some 
original equipment manufacturer burner applications 
may call for a lower pressure to obtain a required fi ring 
rate. Do not change this pressure unless directed to do 
so by the appliance manufacturer.
Install the burner and all wiring in accordance with the 
National Electrical Code and all applicable local codes or 
requirements.
Wire the burner in compliance with all instructions 
provided by the appliance manufacturer. Verify operation 
of all controls in accordance with the appliance 
manufacturer’s guidelines.
See Figure 13 (7505P) or 14 (7184B) for a typical wiring 
diagram (for reference purposes only). 
Wire the Burner
Typical Burner Sequence of Operation - 
7505 Control
Refer to the appliance manufacturer’s wiring diagram for 
actual specifi cations.
Standby: The burner is idle, waiting for a call for 
heat. 
Valve-On Delay: The igniter and motor are on while 
the control delays turning on the oil solenoid valve 
for the programmed time.
Trial For Ignition: The oil solenoid valve is 
energized.  A fl ame should be established within the 
factory set trial for ignition time (lockout time).
Lockout: The control has shut down for one of the 
following safety reasons:
The trial for ignition (lockout) time expired 
without fl ame being established.
The cad cell detected fl ame at the end of the 
Valve On Delay state.
To reset the control from lockout click the button 
1-second.
NOTE: A recurrence of the above failure modes 
or a failed welded relay check could cause the 
control to enter a Hard Lockout state that must 
be reset only by a qualifi ed service technician. 
To reset from Hard Lockout, hold the reset 
button for 15 seconds until the yellow light turns 
on.
Ignition Carryover: Once fl ame is established, 
the igniter remains on for 10 additional seconds to 
ensure fl ame stability.  
1.
2.
3.
4.
a.
b.
5.
Fire or Explosion Hazard
Can cause severe injury, death, or property damage.
The control can malfunction if it gets wet, leading to 
accumulation of explosive vapors.
Never install where water can fl ood, drip or 
condense on the control.
Never use a control that has been wet - replace it.
y
y
y
Electrical Shock Hazard
Electrical shock can cause severe personal 
injury or death.
Disconnect electrical power before installing or 
servicing the burner.
Provide ground wiring to the burner, metal control 
enclosures and accessories. (This may also be 
required to aid proper control system operation)
Perform all wiring in compliance with the National 
Electric Code ANSI/NFPA 70 (Canada CSA C22.1).
y
y
y
Incorrect Wiring Will Result in 
Improper Control Operation
GeniSys 7505 Control wiring label colors may 
not match the wire colors of the burner or other 
manufacturers’ controls.
The GeniSys Control should be wired according to 
the appliance manufacturer’s instructions.
y
y
Section: Wire the Burner