Standby
Motor-off delay
Valve-on delay
Trial for
ignition
Ignition carryover
Run
Lockout
Recycle
9
Pump
prime
Run: With a fl ame established and the control 
continuing to detect a fl ame, the burner will operate 
in the RUN Mode until the load demand is satisfi ed 
or a limit opens. 
If terminals RC1 and RC2 are jumpered, the 
burner operates in the Low-High-Off Mode. 
The burner starts at Low, goes to High after the 
fl ame stabilization period. Flame is extinguished 
when the load is satisfi ed or a limit opens, and 
the burner is sent to motor off delay. 
If a high/low control has been wired between 
terminals RC1 and RC2 the burner starts at 
Low and is released to go High after the fl ame 
stabilization period. It can repeatedly cycle 
between low and high as necessary to meet 
load demand until the load is satisfi ed or a limit 
opens. The  burner is then sent to Motor-off 
Delay. 
Recycle: If the fl ame is lost while the burner is 
fi ring, the control shuts down the burner, enters a 
60 second recycle delay, and repeats the ignition 
sequence.  The control will continue to Recycle each 
time the fl ame is lost, until it reaches a pre-set time 
allotment.  The control will then go into Hard Lockout 
instead of recycle.  This feature prevents excessive 
accumulation of oil in the appliance fi ring chamber.
6.
a.
b.
7.
Motor-Off Delay: The oil solenoid valve is turned 
off and the control delays turning the motor off 
for the set motor-off delay time before the control 
returns to standby.
Pump Prime: The igniter and motor are on with the 
oil solenoid valve energized for 4 minutes.  During 
Pump Prime mode, the cad cell is disregarded, 
allowing the technician to prime the pump without 
having to jumper the cad cell.
8.
9.
Section: Wire the Burner
Display Module:
Permanent device for 
programming and diagnostics
Alarm Module:
For adding isolated low voltage 
alarm contacts to the base control. 
See Alarm Module Instructions for 
specifi cations.
Contractor’s Tool:
Hand-held device for 
programming and diagnostics
Cad Cell
Connections
Wiring 
Connections
Communication Port 2
Reset Button
with Red Light
Communication Port 1
Thermostat Terminals
Green Light
Yellow Light
Optional Components:
Figure 12 - GeniSys 7505 Control with Optional Components
Figure 11 - Typical Burner Sequence of Operation - 7505