Set “Z” Dimension
Replace the rear access door on the burner, making 
sure that the adjusting plate assembly is seated in 
the recessed area in the housing.
Loosen acorn nut (item c) and spline nut (item b).  
Move nozzle line forward to the maximum head 
setting #9 and tighten acorn nut (item c).
Loosen acorn nut (item d). Slide the nozzle line 
and plate assembly until dimension “Z” in Figure 6 
is 1-3/4” ±1/16” (CF1400 and CF2300). When 
dimension “Z” (from end of air tube to fl at area of 
front face of head) is correctly set, tighten acorn nut 
(item d). Verify that the adjusting plate assembly is 
properly seated in the recessed area in the housing.  
Tighten spline nut (item b) fi nger tight.
Attach the oil line from the oil valve to the nozzle 
line end. Tighten securely.
Before proceeding, check dimension “Z” once 
again. Loosen acorn nut (item d) if necessary to 
reposition the nozzle line. Once dimension “Z” is 
set, do not loosen acorn nut (item d) again. 
Loosen acorn nut (item c) to set the head at the 
proper setting for the application and tighten splined 
nut securely.
Insert Burner
Position the burner in the front of the appliance and 
loosely tighten the nuts on the mounting studs. The 
burner should be pitched downward 2° as shown in 
Figures 3 and 4.
See Figure 8. Install the pedestal support kit 
(recommended) by attaching the 3/4” NPT fl ange 
(item a) to the bottom of the burner using the (4) #10 
screws provided. Cut and thread (one end only) a 3/4” 
pipe nipple (item bwith length 11 inches less than 
dimension D
 in Figure 8. Thread the pipe into the fl ange. 
Secure the burner to the appliance by tightening the nuts 
on the burner fl ange mounting studs. 
1.
2.
3.
4.
5.
6.
Figure 7 – Adjusting Plate Assy.
Fuel Unit By-pass Plug
Factory-Installed Pump 
Bypass Plug 
Failure to follow these guidelines will cause the fuel 
pump seals to rupture and result in oil leakage, burner 
malfunction and potential fi re and injury hazards.
Models CF1400 and CF2300 are shipped with the 
pump bypass plug installed.
Do not remove the bypass plug from the pump. It is 
required for step-fi ring (Lo/Hi) operation.
Do not operate the burner unless a return line or 
bypass loop is installed or the pump seal will rupture.  
Carefully comply with the following instructions 
provided in this section of the manual.
y
y
y
y
Install Oil Supply To 
Specifi cations
Failure to properly install the oil supply system 
could cause oil leakage, equipment malfunction, 
puff-back of hot gases, heavy smoke, 
asphyxiation, explosion and fi re hazards.
Carefully install the oil supply lines, fi ttings and 
components using the guidelines provided in this 
section.
The oil supply must comply with the latest edition 
of NFPA 31 (Canada CSA B139) and all applicable 
codes.
Do NOT install valves in the return line.
If the oil supply inlet pressure to the pump exceeds 3 
psig or for gravity feed systems, install an oil safety 
or pressure reducing valve (Webster OSV, Suntec 
PRV or equivalent). 
y
y
y
y
Figure 8 – Burner Installed in Appliance Front
Section: Mount the Burner
Legend
H
Housing total length (CF1400 - 18”, CF2300 - 18.5”)
J
Center to bottom of housing (CF1400 - 10.88”, CF2300 - 10.5”)
K
Overall housing height (CF1400 - 13.63”, CF2300 - 15.63”)
d
b
e
f
c
g
#
9 Setting