 Normal Operation 
29
Page
 
 
TEMPERATURE SETTINGS
 
‐Without remote controller‐ 
There  are  4  temperatures  that  you  can  select  from  by  changing  the  dipswitch  settings  on  the 
computer board without the remote controller. See the table below.  
Temperatures available 
113
122
131
140
For detailed dipswitch settings for each temperature, refer to the next page. 
  The temperature has been preset at the factory to 122°F (50°C).  
  If  temperatures  other  than  the  ones  listed  above  are  required,  the  remote  controller  can 
provide several more temperature options.  Refer to p. 9 for a list of available temperatures on 
the remote controller.  
  This  water  heater  is  an  on‐demand,  tankless  water  heater  designed  to  efficiently  supply 
endless hot water without reference to temperature settings. 
 
 
 
 
 
 
       
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Dipswitches  
‐Dipswitch settings for each temperature on the computer board‐
(45
OFF
ON
C)
113 F
1 2 3 4 5 6 7 8
OFF
ON
1 2 3 4 5 6 7 8
(50 C)
122 F
DEFAULT
(55
OFF
ON
C)
131 F
1 2 3 4 5 6 7 8
(60
OFF
ON
C)
140 F
1 2 3 4 5 6 7 8
Temperature Settings     
  Turn off the power supply to the 
water heater before changing the 
dipswitch settings. 
  Only change the switches with the 
dark squares. The dark squares 
indicate which direction the 
dipswitch should be set to.
WARNING