Device Operations
Devices
Bootloader
In this mode, the device cannot participate in a mesh and cannot provide fire protection.  The 
device will be available in the communicator window of the PC Tool with a status “Bootloader”.
To get a device out of bootloader, refer to the Appendix C:, "Troubleshooting and Testing".
Distributor
In this mode the device is functioning as a profile distributor.  The device cannot participate in a 
mesh and cannot provide fire protection.  It can be used to share the profile with any device that 
requests a profile.  The device will be available in the communicator window of the PC Tool with a 
status “Distributor”.
Mesh Participant
Devices that are in the mesh network, no longer communicates directly with the PC Tools applica-
tion.  The PC Tools application must communicate with the FWSG for status information from the 
device.  The FWSG will respond to the FACP for the device at the address set with the code wheels.  
The following states are applicable for a device in a mesh network.
Mesh Formation Mode
In this mode, the devices are active participants in a mesh that is forming. The LED flashes in the 
following pattern. First blink green, second blink yellow every 6.8 seconds. The device cannot per-
form any fire protection in this state.  The device responds to its SLC address with a “DEVICE 
INIT” or “INIT” trouble.
For further information on mesh formation mode, refer to the topic “Mesh Formation”.
Initial Mesh Optimization Mode
In this mode, the mesh network is formed and is in the process of establishing stronger communica-
tion paths. The LED pattern flashes in the following pattern.  Single yellow blink every 6.8 sec-
onds. The device cannot perform any fire protection in this state.  The device responds to its SLC 
address with a "DEVICE INIT" or "INIT" trouble.
For further information on initial mesh optimization mode, refer to the topic, “Initial Mesh Optimi-
Normal Mode
In the normal mode, the mesh network is formed and provides fire protection. The LED pattern is 
single green blink every 13.6 seconds. The LED flash can be disabled by panel configuration. If a 
device is in trouble, it will be indicated by the trouble states.  For information on trouble states, 
Rescue Mode
In the rescue mode, devices that are active participant in the mesh search and retrieve the devices 
that have lost the communication link. The rescue mode is indicated by the LED pattern of 1 green 
blink every 6.8 seconds.  For more information on rescue mode, refer to the topic, “Rescue Mode”.
3.7.2  LED Indications
The two LEDs on the devices blink in the same pattern to allow the LED to be viewed from any 
angle.  The LED indications are provided in the table below: