Honeywell International Inc. THX9001R01 Manuale Utente

Pagina di 28
CTK03 ComfortNet™ Communicating Thermostat
11
I/O-CHTSTAT03  69-2688—01
Mount optional accessories
1  Mount the sensor on a vertical
exterior wall, at least 6 inches below
any overhang. Choose a location
protected from direct sunlight.
2  Place sensor securely in bracket,
facing away from wall.
5
M28491
M28849A
[If no sensors are used, skip to Section 6.]
To install outdoor air sensor
To install indoor air sensor
To install Entry/Exit Remote or Vent Boost Remote
1  Remove the wallplate and mount it 4
to 6 feet above the floor on an interior
wall. Drill 3/16-inch holes for drywall,
7/32-inch for plaster.
2  Attach sensor securely to wallplate as
shown.
Mounting the remote is optional.
1  Remove the front cover from the
remote.
2  Use provided screws and wall
anchors to fasten the remote to the 
wall. Drill 3/16-inch holes for drywall,
7/32-inch for plaster.
3  Replace the cover on the remote.
M32936A
M33095
Do not install the indoor air sensor where it can be affected by:
Drafts or dead spots behind doors and in corners.
Hot or cold air from ducts.
Radiant heat from sun or appliances.
Concealed pipes and chimneys.
Unheated (uncooled) areas such as an outside wall