Switch Configuration
FIGURE 2
Switch description and default settings:
SW1-1 Hardware Identity
When set in the “ON” position the unit is configured for “Wiegand” Interface. The “OFF” position configures the unit
for “Clock and Data” Interface.
SW1-2  Beeper Control - On
The Beeper may be enabled or disabled to sound when an access card is read.  When enabled, the audible tone is
sounded when the a card is successfully read.  When the Beeper is disabled, the only method to activate the Beeper
is to use the external Beeper control line. The Beeper will turn on when the control line is switched to ground.  Switch
2 in the "on" position enables the beeper (the default).
SW1-3 Green LED Control
The Green LED can be configured to turn on, or not turn on when an access card is read. Switch 3 in the “off”
position selects the Green LED to be turned on (the default).
SW1-4 Keyboard Operation - Off
Not Available.
SW1-5 LED Dual mode - Off
The default mode for the LED control is the single line control.  The LED is normally red and when the access control
card is read the LED flashes Green. When “On”, this mode allows the user independent control of both Red and
Green LED’s. This is referred to as the Dual LED mode.  When the Red or Green LED Control line is switched to
ground the respective LED is turned ON.  If both LED’s are on the LED appears to glow amber.
SW1- 6 and 7 Data0 and Data1 output pull-up resistor - On, On
The data outputs may be configured as open collector or have pull-ups connected to 5VDC through 1kOhm resistors
in the reader.  The default (standard) configuration is pull-ups connected, with switches 6 and 7 "On" .  Note: When
the outputs are configured as open collector, the host panel should provide pull-ups and bias voltage at the panel
inputs.
SW1-8
Not used