ADEMCO 5821
Temperature Sensor & Flood Detector
 
INSTALLATION AND SETUP GUIDE 
GENERAL INFORMATION 
The ADEMCO 5821 Temperature Sensor & Flood Detector 
is a wireless transmitter used with Honeywell’s ADEMCO 
alarm systems that support 5800 series devices.  The 5821 
can be configured to operate as a stand-alone temperature 
sensor and/or as either a Remote Temperature Sensor or 
Flood Detector.  The 5821 in combination with the 
ADEMCO T280R temperature probe is ideal for monitoring 
refrigerators and freezers in restaurants, kitchens and 
warehouses where food storage is a concern.  The 5821 in 
combination with the ADEMCO 470PB probe can be used to 
sense floods in basements and other areas where there is a 
possibility of flooding.  The 5821 will send an alarm, via its 
RF transmitter, to the control when the preset temperature 
limit is exceeded or when a flood is detected.  Temperature 
monitoring and flood detection is dependent on the 
operating mode selected.  Refer to Table 1 for applicable 
operating modes.   
Room temperature is monitored at the device using the 
5821’s internal sensor.  Refrigerator or Freezer temperature 
is monitored remotely using the ADEMCO T280R 
temperature probe.  Flood detection is monitored remotely 
using the ADEMCO 470PB probe with the supplied resistor.  
A separate 5821 is required for each external probe being 
used.   
In refrigerator or freezer applications, when the 
temperature increases past the high threshold limit and a 
delay of greater than 30 minutes passes, an alarm is 
triggered.  This preset delay offers greater reliability 
against false alarms, especially due to open refrigerator or 
freezer doors.   
A 3-volt lithium battery powers the 5821.  If the battery 
voltage gets too low, the 5821 sends a low battery signal to 
the control panel. 
   
INSTALLING/REPLACING THE BATTERY 
Important Notes:   
•  Use 3-volt lithium battery:   
Duracell DL 123A or Panasonic CR123A.   
•  Observe polarity.   
•  When replacing the battery, wait at least 30 seconds 
after removing the old battery, before installing the new 
one. 
Install or replace the battery as follows:   
1.  Remove the transmitter's top cover by inserting the flat 
blade of a small screwdriver into the pry-off slot at one 
end of the unit (see Figure 1 for location), and slightly 
twisting the blade until the cover disengages.   
2.  Install a 3-volt lithium battery as shown in Figure 1.  
 
TAMPER SUPERVISION 
The 5821 tamper supervision feature (Loop 4) causes a 
trouble signal to be sent to the control if the unit’s cover is 
removed from the base or if an external probe is used and 
the wire is cut (open) or the probe is shorted.   The tamper 
switch is also used to program the unit’s serial number and 
loop assignments to the control panel. 
SETTING THE OPERATING MODE 
Table 1 provides a list of the various operating modes of the 
5821 with the respective Loop and DIP Switch settings for 
each.    Note  that  Cold  Temp  Sensing  can  be  used  in 
combination with any of the other operating modes.  To use 
the transmitter to monitor two different conditions, you 
must program each loop used on the 5821 as its own zone, 
and you must set the DIP Switches as shown for the 
combination functions in Table 1. 
PROGRAMMING THE UNIT 
Once you have selected an operating mode and have set the 
DIP Switches accordingly, you must enroll the transmitter 
in the control panel.  When programming the transmitter in 
the control panel, note that you must program a separate 
zone for each loop you are using on the transmitter.  To 
program:    
 
1.  Enter the control’s Zone Programming mode.   
2.  Enter the zone number to be programmed. 
3.  Enter the applicable zone type when prompted (zone 
types such as 24-Hr. Aux, Waterflow, etc. should be 
used) depending on the function of the zone and the 
control panel being used (see the control panel’s 
instructions for available zone types and definitions). 
4.  When prompted, enter Input Type 03 (3 on some 
controls) – Supervised RF Transmitter.   
5.  When prompted for the serial number, transmit from 
the detector by pressing the tamper switch.    
6.  When the serial number is displayed, transmit from the 
detector again by pressing the tamper switch.   
The current loop number (4) will begin to flash.   
7.  Manually change the loop number to the desired loop 
number for the zone (according to the application—see 
Table 1). 
8.  When programming for this zone is complete, program 
other zones for the transmitter as necessary (each loop 
requires its own zone.  
9.  Exit Programming mode when programming is 
complete, and test the detector.  Refer to the Testing 
section. 